Review Stop P
Sequence Number 1
Notes
Date Text
2020-01-13 11:07:011) INDICATE THE OCCUPANCY TYPE ON THE PLANS PER 2017
 FBC - BUILDING SEC. 302.
 2) INDICATE THE OCCUPANCY LOAD ON THE PLANS PER 2017
 FBC-BUILDING SEC. 1104 & TABLE 1004.1.2.
 3) SHT.A1.0 REFERS TO THE 2014 FBC. THE CODE IN EFFECT
 IS THE 2017 FBC. REVISE THE NOTE.
 4) SHT. A2.0 & SHT.P1.1 SHOWS AN EXTERIOR SHOWER. WHAT
 WILL THIS SHOWER BE USED FOR? CLARIFY ON THE PLANS. WPB
 AMEND. TO FBC SEC. 107.1. DETAIL 1 ON P1.1 CALLS THIS
 OUT AS A CONDENSATE WELL AND CONDENSATE LINE. CLARIFY.
 5) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS
 SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A
 HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017
 FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE CALLS
 OUT FLAT PAINT. THIS DOES NOT COMPLY.
 6) WALLS AND PARTITIONS WITHIN 2 FEET OF WATER CLOSETS
 SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A
 HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017
 FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE ON
 SHT.A6.0 DOES NOT SPECIFY THE HEIGHT OF THE
 TILE.CLARIFY.
 7) AN UNDER THE SINK GREASE TRAP MAY BE REQUIRED.
 8) SHT. A2.1 - THE TOP OF THE LAVATORY IN THE TOILET
 ROOM SHALL BE LOCATED A MAXIMUM OF 34 INCHES TO THE TOP
 OF THE RIM PER 2017 FBC - ACCESS. SEC.606.3.
 9) A MINIMUM CLEARANCE OF 27 INCHES SHALL BE PROVIDED
 UNDER THE LAVATORY PER 2017 FBC SEC.306.3.
 10) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS
 SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE
 REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH
 FLOOR OR GROUND.2017 FBC-ACCESS. SEC.603.3.
 11) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7
 INCHES MINIMUM AND 9 INCHES MAXIMUM FROM THE FRONT OF
 THE WATER CLOSET TO THE CENTERLINE OF THE DISPENSER.
 2017 FBC ACCESS. SEC.604.7.
 12) THE DISHWASHER, ICE MACHINE, AND COFFEE MACHINE
 SHALL BE EQUIPPED WITH AA BACKFLOW DEVICE PER 2017
 FBC-PLUMBING SEC.608.2, 608.3, 608.16.10,
 13) A RECIRCULATION LINE MAY BE REQUIRED FOR THE HOT
 WATER SYSTEM IF THE DEVELOPED LENGTH OF THE HOT WATER
 PIPING EXCEEDS 50 FEET FROM THE SOURCE OF HOT WATER TO
 THE FIXTURES THAT REQUIRE HOT WATER PER 2017
 FBC-PLUMBING SEC.607.2.
 14) SHT. P1.1 - SHOW THE SIZE OF THE EXPANSION TANK ON
 THE PLANS.
 15) TEMPERED WATER IS REQUIRED TO THE LAVATORY IN THE
 TOILET ROOM PER 2017 FBC-PLUMBING SEC.607.1, 416.5.
 16) SHT. IR-1 - IRRIGATION SCHEDULE - THE BACKFLOW
 PREVENTER FOR THE IRRIGATION SHALL BE LEAD FREE. 2017
 FBC-PLUMBING SEC.605.2. THE 975 XL BACKFLOW DEVICE IS
 NOT LEAD FREE.
 17) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW
 PREVENTION DEVICE AND MUST BE TESTED AND CERTIFIED BY
 THE CITY OF WEST PALM BEACH UTIITIES DEPT. PER THE CITY
 OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW