Date |
Text |
2020-01-13 11:07:01 | 1) INDICATE THE OCCUPANCY TYPE ON THE PLANS PER 2017 |
| FBC - BUILDING SEC. 302. |
| 2) INDICATE THE OCCUPANCY LOAD ON THE PLANS PER 2017 |
| FBC-BUILDING SEC. 1104 & TABLE 1004.1.2. |
| 3) SHT.A1.0 REFERS TO THE 2014 FBC. THE CODE IN EFFECT |
| IS THE 2017 FBC. REVISE THE NOTE. |
| 4) SHT. A2.0 & SHT.P1.1 SHOWS AN EXTERIOR SHOWER. WHAT |
| WILL THIS SHOWER BE USED FOR? CLARIFY ON THE PLANS. WPB |
| AMEND. TO FBC SEC. 107.1. DETAIL 1 ON P1.1 CALLS THIS |
| OUT AS A CONDENSATE WELL AND CONDENSATE LINE. CLARIFY. |
| 5) WALLS AND PARTITIONS WITHIN 2 FEET OF SERVICE SINKS |
| SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A |
| HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017 |
| FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE CALLS |
| OUT FLAT PAINT. THIS DOES NOT COMPLY. |
| 6) WALLS AND PARTITIONS WITHIN 2 FEET OF WATER CLOSETS |
| SHALL HAVE A SMOOTH, HARD NONABSORBANT SURFACE TO A |
| HEIGHT NOT LESS THAN 4 FEET ABOVE THE FLOOR.PER 2017 |
| FBC-BUILDING SEC.1210.2.2. THE FINISH SCHEDULE ON |
| SHT.A6.0 DOES NOT SPECIFY THE HEIGHT OF THE |
| TILE.CLARIFY. |
| 7) AN UNDER THE SINK GREASE TRAP MAY BE REQUIRED. |
| 8) SHT. A2.1 - THE TOP OF THE LAVATORY IN THE TOILET |
| ROOM SHALL BE LOCATED A MAXIMUM OF 34 INCHES TO THE TOP |
| OF THE RIM PER 2017 FBC - ACCESS. SEC.606.3. |
| 9) A MINIMUM CLEARANCE OF 27 INCHES SHALL BE PROVIDED |
| UNDER THE LAVATORY PER 2017 FBC SEC.306.3. |
| 10) MIRRORS LOCATED ABOVE LAVATORIES OR COUNTERTOPS |
| SHALL BE INSTALLED WITH THE BOTTOM EDGE OF THE |
| REFLECTING SURFACE 40 INCHES MAXIMUM ABOVE THE FINISH |
| FLOOR OR GROUND.2017 FBC-ACCESS. SEC.603.3. |
| 11) THE TOILET PAPER DISPENSER SHALL BE LOCATED 7 |
| INCHES MINIMUM AND 9 INCHES MAXIMUM FROM THE FRONT OF |
| THE WATER CLOSET TO THE CENTERLINE OF THE DISPENSER. |
| 2017 FBC ACCESS. SEC.604.7. |
| 12) THE DISHWASHER, ICE MACHINE, AND COFFEE MACHINE |
| SHALL BE EQUIPPED WITH AA BACKFLOW DEVICE PER 2017 |
| FBC-PLUMBING SEC.608.2, 608.3, 608.16.10, |
| 13) A RECIRCULATION LINE MAY BE REQUIRED FOR THE HOT |
| WATER SYSTEM IF THE DEVELOPED LENGTH OF THE HOT WATER |
| PIPING EXCEEDS 50 FEET FROM THE SOURCE OF HOT WATER TO |
| THE FIXTURES THAT REQUIRE HOT WATER PER 2017 |
| FBC-PLUMBING SEC.607.2. |
| 14) SHT. P1.1 - SHOW THE SIZE OF THE EXPANSION TANK ON |
| THE PLANS. |
| 15) TEMPERED WATER IS REQUIRED TO THE LAVATORY IN THE |
| TOILET ROOM PER 2017 FBC-PLUMBING SEC.607.1, 416.5. |
| 16) SHT. IR-1 - IRRIGATION SCHEDULE - THE BACKFLOW |
| PREVENTER FOR THE IRRIGATION SHALL BE LEAD FREE. 2017 |
| FBC-PLUMBING SEC.605.2. THE 975 XL BACKFLOW DEVICE IS |
| NOT LEAD FREE. |
| 17) A SEPARATE PERMIT IS REQUIRED FOR THE BACKFLOW |
| PREVENTION DEVICE AND MUST BE TESTED AND CERTIFIED BY |
| THE CITY OF WEST PALM BEACH UTIITIES DEPT. PER THE CITY |
| OF WEST PALM BEACH CROSS CONNECTION CONTROL MANUAL. |
| |
| TIM LARGE |
| CHIEF PLUMBING INSPECTOR |
| PLUMBING PLAN REVIEW |