Plan Review Notes
Plan Review Notes For Permit 19081158
Permit Number 19081158
Review Stop M
Sequence Number 1
Notes
Date Text
2020-01-15 11:12:401ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19081158
 1/15/20
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW SYSTEM- SECTION 312.1 FBC M.
  
 2) M1 & A6.0: INDICATE THAT A NON-COMBUSTIBLE BI-FOLD
 DOOR WILL ENCLOSE THE AC CLOSET- SEE SECTION 602.1 FBC
 M.
  
 3) M1: SHOW THE TOILET AND MOP SINK CLOSET EXHAUST DUCT
 RUNS AND TERMINATION LOCATIONS- SECTION 501.3.1 FBC M.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  