Plan Review Notes For Permit 19081158 |
Permit Number |
19081158 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2020-01-15 11:12:40 | 1ST REVIEW FBC-2017 MECHANICAL | | PERMIT #19081158 | | 1/15/20 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | 1) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE | | NEW SYSTEM- SECTION 312.1 FBC M. | | | | 2) M1 & A6.0: INDICATE THAT A NON-COMBUSTIBLE BI-FOLD | | DOOR WILL ENCLOSE THE AC CLOSET- SEE SECTION 602.1 FBC | | M. | | | | 3) M1: SHOW THE TOILET AND MOP SINK CLOSET EXHAUST DUCT | | RUNS AND TERMINATION LOCATIONS- SECTION 501.3.1 FBC M. | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | | | | | | | | | |
|