2020-01-30 10:10:24 | PLAN |
| REVIEW COMMENTS |
| |
| 1ST REVIEW: FBC SIXTH EDITION (2017) |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| 1) THE GOVERNING CODES ON SHEET AO ARE INCORRECT. THIS |
| PROPOSED PROJECT IS THE CONVERSION OF AN EXISTING |
| SINGLE FAMILY DWELLING TO A COMMERCIAL USE AS A JUICE |
| BAR AND YOGA STUDIO. THE SIXTH EDITION (2017) FBC |
| EXISTING BUILDING AND FBC BUILDING ARE THE GOVERNING |
| CODES. THE CLASSIFICATION OF WORK FROM THE EXISTING |
| BUILDING CODE SECTION 506 WOULD BE CHANGE OF OCCUPANCY. |
| SECTIONS 508 HISTORIC BUILDINGS AND SECTIONS 509 |
| RELOCATED BUILDINGS MAY ALSO APPLY. |
| |
| 2) GENERAL NOTE #1 ON SHEET A1.0 SPECIFIES THE FIFTH |
| EDITION (2014) FBC RESIDENTIAL. THIS IS INCORRECT. |
| PLEASE UPDATE NOTES. |
| |
| 3) THE STRUCTURAL PLAN SHEETS NEED TO BE UPDATED TO |
| REFERENCE THE 2017 FBC RATHER THAN THE 2014 FBC. |
| |
| 4) SPECIFY THE AREA TABULATIONS ON THE PLANS. FBC |
| 107.2.1.2 |
| |
| 5) SPECIFY OCCUPANCY TYPE AND OCCUPANT LOAD ON THE |
| PLANS. FBC 302 & 1004 IT APPEARS THAT DUE TO SMALL SIZE |
| BUILDING AND THE YOGA AREA THAT THERE WILL BE LESS THAN |
| 50 PERSONS WHICH WOULD ALLOW THIS TO BE CLASSIFIED AS A |
| BUSINESS OCCUPANCY. SEE SECTIONS 303.1.1, 303.1.2 AND |
| 304.1. |
| |
| 6) PROVIDE A LIFE SAFETY PLAN. SHOW THE OCCUPANT LOADS, |
| REQUIRED NUMBER OF EXITS, EXIT PATHS OF TRAVEL, EXIT |
| ACCESS TRAVEL DISTANCE, EXIT AND EXIT ACCESS DOOR SIZES |
| (CAPACITY AND ACTUAL NUMBER OF OCCUPANTS SERVED), ETC. |
| FBC CHAPTER 10. |
| |
| 7) SHOW COMPLIANCE WITH SIXTH EDITION (2017) FBC |
| ACCESSIBILITY. THE PROPOSED RAMP DOES NOT MEET ALL OF |
| THE ADA REQUIREMENTS FOR A RAMP. A 60" X 60" MINIMUM |
| CLEAR LANDING IS REQUIRED BETWEEN RAMP RUNS WHEN THERE |
| IS A CHANGE OF DIRECTION PER SECTION 405.7.4. |
| |
| 8) THE RAMP HANDRAILS ARE REQUIRED TO COMPLY WITH FBC |
| ACCESSIBILITY SECTION 505 INCLUDING TOP AND BOTTOM |
| EXTENSIONS. |
| |
| 9) THE STAIRS ARE REQUIRED TO COMPLY WITH FBC |
| ACCESSIBILITY SECTIONS 504 STAIRWAYS AND 505 HANDRAILS. |
| |
| 10) THE ACCESSIBLE DOORS ARE REQUIRED TO COMPLY WITH |
| FBC ACCESSIBILITY 404, INCLUDING SECTION 404.2.5 FOR |
| MAXIMUM 1/2" HIGH THRESHOLDS. |
| |
| 11) THE SALE/SERVICE COUNTER IS REQUIRED TO COMPLY WITH |
| FBC ACCESSIBILITY SECTION 904.4.2. IT APPEARS THAT YOU |
| INTEND TO PROVIDE FOR A FORWARD APPROACH SINCE THE |
| ACCESSIBLE COUNTER SPACE IS 30" WIDE. HOWEVER, SECTION |
| 904.4.2 REQUIRES KNEE AND TOE SPACE UNDER THE COUNTER |
| COMPLYING WITH SECTION 306. I DID NOT SEE A DETAIL FOR |
| THIS ON THE PLANS. PLEASE CLARIFY. |
| |
| 12) SHEET S-1 OF THE STRUCTURAL PLANS SPECIFIES A FLOOR |
| LIVE LOAD OF 40 PSF WHICH IS FOR RESIDENTIAL. PLEASE |
| REVIEW FBC 1603.1 & 1607 TO DETERMINE THE FLOOR LIVE |
| LOADS FOR THIS PROJECT. |
| |
| 13) PROVIDE ROOF FRAMING DETAILS FOR THE 2 X 6 RAFTERS, |
| CEILING JOISTS, RIDGE BOARD, COLLAR TIES, GABLE END |
| FRAMING AND BRACING, ETC. SPECIFY THE RAFTER TO RIDGE |
| CONNECTIONS. FBC CHAPTER 23 THE SECTIONS ON THE ROOF |
| FRAMING PLAN ON SHEET S-2 ARE FLOOR DETAILS. |
| |
| 14) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A |
| RESPONSE LETTER ADDRESSING EACH REVIEW COMMENT ALONG |
| WITH THE CITY RE-SUBMITTAL FORM. THIS WILL ALSO HELP |
| REDUCE PLAN REVIEW TIME. |
| |
| |
| |