Plan Review Notes For Permit 19081140 |
Permit Number |
19081140 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-09-11 16:35:14 | ***CORRECTIONS*** | | PETER E VALENTI | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6673 | | | | FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | FBC R = FBC RESIDENTIAL | | FBC M = FBC MECHANICAL | | | | BUILDING REVIEW DENIED: | | | | 1. FBC B 107.2.1 PLEASE CLARIFY THAT AWNING AND | | LETTERING WILL NOT BE COVERED BY THIS PERMIT. | | | | 2. FBC B 3301.1/FBC B 3301.2 PROVIDE INFORMATION ON HOW | | SAFETY DURING CONSTRUCTION AND PROTECTION OF ADJACENT | | PROPERTIES WILL BE MAINTAINED AS WELL AS THE SAFE | | STORAGE AND PLACEMENT OF MATERIALS AND EQUIPMENT DURING | | PROJECT. |
|