Date Text
2019-09-16 13:47:032017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19081131
 ADD: 3800 WASHINGTON RD. SUITE: 1211
 CONT: PILLAR CONSTRUCTION
 TEL: 561-317-4042
 E-MAIL: [email protected]
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: MON. SEPT. 16/ 2019
 ACTION: DENIED
  
 1) SHEET 2 OF 3 SHOWS IN DETAIL # 2 A SUSPENDED GRID
 SUSPENSION SYSTEM. WHAT THIS DETAIL NOR ANY OTHER
 DETAIL INDICATING HOW THE HANGING WIRE IS TO BE
 FASTENED TO THE STRUCTURAL CONCRETE DECK ABOVE NOR
 SPACING OF THE ANCHORS. THE PLANS ARE ALSO SILENT AS TO
 THE TYPE OF CONCRETE DECK POST TENSIONED SLAB,
 REQUIRING X-RAY FOR THE LOCATION OF TENDONS OR A
 CONVENTIONAL CONCRETE SLAB & REBAR SYSTEM? 2017 FBC-B
 TABLE 2508.1/ ASTM C754.
  
 2) SHEET 2 OF 3 SHOWS DETAIL # 2 WITH THE MAIN BEAMS
 BEING 1 ? INCH COLD ROLLED CHANNEL AND 7/8 INCH
 HIGH-HAT FURRING CHANNEL. WHAT THIS DETAIL INDICATES
 THE MAIN HANGER WIRE HANGER WIRE SPACING IS TO BE 4
 FEET ON CENTER. THE PLANS ARE SILENT AS TO THE GAUGE OF
 THE WIRE SIZE? 2017 FBC-B TABLE 2508.1/ ASTM C754. (6)
 SUSPENDED AND FURRED CEILINGS. MINIMUM OF # 12 GAUGE
 GALVANIZED SOFT ANNEALED, MILD STEEL WIRE. PLEASE
 UPDATE PLANS.
  
 3A) SHEET 2 OF 3 DETAIL 2 SHOWS THE HANGER WIRE
 ATTACHING TO THE MAIN RUNNER/ BEAM. THE PLANS ARE
 SILENT TO THE NUMBER OF WRAPS THE HANGER WIRE ONCE
 AROUND THE MAIN RUNNER IS TO WRAP AROUND ITSELF. ASTM
 C754. (6) SUSPENDED AND FURRED CEILINGS. SECTION 6. 1.
 3 TO DEVELOP THE FULL STRENGTH OF THE HANGER WIRE A
 MINIMUM OF 3 WRAPS AROUND ITSELF AND WITHIN 3 INCHES.
 PLEASE UPDATE PLANS.
  
 3B) THE PLANS ARE ALSO SILENT AS TO THE FASTENING OF
 THE 7/8 INCH HI-HAT CHANNEL TO THE MAIN RUNNER CHANNEL?
 PLEASE ALSO REFER TO ASTM C754 SECTION 6.1.3 REQUIRING
 A SADDLE TIE AROUND THE MAIN RUNNER AND FURRING
 MEMBERS. PLEASE UPDATE PLANS.
  
 3C) SHEET 2 OF 3 DETAIL 4 SHOWS THE HANGER WIRES AT 4
 FEET ON CENTER BUT DOES NOT INDICATE WHAT HAPPENS
 WITHIN THE LAST 4 FEET FROM THE WALL, THE HI-HAT IS
 LEFT FLOATING? PLEASE REVIEW ASTM C754 6.5.1 A CHANNEL
 SHALL BE LOCATED WITHIN 6 INCHES OF THE PARALLELING
 WALLS TO SUPPORT THE ENDS OF THE CROSS FURRING. THE
 ENDS SHALL BE SUPPORTED BY HANGER WIRE NOT LESS THAN 6
 INCHES FROM SUCH ENDS.
  
 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  