Plan Review Notes
Plan Review Notes For Permit 19081080
Permit Number 19081080
Review Stop G
Sequence Number 1
Notes
Date Text
2019-08-22 16:04:4908/22/2018 1ST GAS REVIEW **DENIED** WITH COMMENTS.
  
 NOTE: A FULL AND COMPREHENSIVE PLAN REVIEW COULD NOT BE
 ACCOMPLISHED AT THIS TIME DUE TO THE QUALITY OF THE
 SUBMITTED PLANS. ADDITIONAL COMMENTS MAY BE GENERATED
 ON THE RESUBMITTAL REVIEW.
  
 1. GAS RISER DIAGRAM REQUIRED, SUBMIT AN ISOMETRIC
 DRAWING THAT CLEARLY SHOWS, UNIONS, SHUTOFF VALVES ON
 SYSTEM, REGULATOR AND THE LENGTH OF ALL CUT SECTIONS OF
 PIPE PER THE 2017 FBC RES. SECS. G2413.4.1, G2413.4.2.
  
 2. SUBMIT TWO COPIES OF THE SIZING TABLE USED IN THE
 DESIGN FOR THE GAS SYSTEM OR PLACE A NOTE ON BOTH SETS
 OF PLANS LISTING THE SIZING TABLES FROM GAS CODES OR
 ANOTHER STANDARD THAT WERE USED IN THE DESIGN OF THIS
 SYSTEM PER THE 2017 FBC RES. SEC. G2413.3
  
 3. THE ADDRESS OF THE PROJECT OR RESIDENCE MUST BE ON
 PLAN. WPB AMENDMENTS TO THE FBC SEC.107.2.1 INFORMATION
 ON CONSTRUCTION DOCUMENTS.
  
 4. TYPE OF GAS LABELED ON PLANS PER THE WPB AMENDMENTS
 TO THE FBC SEC. 107.2.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS.
  
 5. INDICATE THE DELIVERY PRESSURE (PSI) OF THE SYSTEM
 ON THE PLAN PER 2017 FBC FG SEC. 402.2 OR 2017 FBC FG
 RES. SEC. G2413.2.
  
 6. SUBMIT MANUFACTURER?S SPECIFICATIONS FOR THE
 PRESSURE REGULATORS. REGULATORS INSTALLED ON THE
 EXTERIOR OF THE BUILDING SHALL BE APPROVED FOR OUTDOOR
 INSTALLATION PER THE 2017 FBC RES. SEC. G2421.1.
  
 7. SUBMIT MANUFACTURER?S SPECIFICATION
 SHEETS/INSTALLATION MANUAL FOR POOL HEATER EQUIPMENT TO
 VERIFY COMPLIANCE WITH 2017 FBC FG RES. SEC. G2408.1.
 THE POOL HEATER SHALL HAVE A MINIMUM THERMAL EFFICIENCY
 OF 82% PER THE 2017 FBC-ENERGY SEC. R403.10.4.
  
 8. IN 2013 THERE WHERE GAS APPLIANCES INSTALLED, AND
 THE BTU?S ARE DIFFERENT FROM THE ONES SUBMITTED. THE
 GAS TANKLESS IS 180 BTU?S AN THE NEW ONE IS 160 BTU?S
 PLEASE CLARIFY PER THE 2017 FBC RES. SEC. G2413.
  
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION, MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 LUIS A. CRESPO
 PLUMBING INSPECTOR /
 PLUMBING PLAN REVIEW
 AVAILABLE FROM 1:00 PM TO 4:00 PM
 [email protected]
  