Plan Review Notes
Plan Review Notes For Permit 19081039
Permit Number 19081039
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-08-22 13:24:57THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
  
 1) THERE IS INDICATIONS OF UNDERGROUND WORK.
  
 PLEASE CLARIFY IF THIS PERMIT IS INTENDED TO COVER ALL
 UNDERGROUND WORK AS WELL AS FOR THE ABOVE GROUND
 SPRINKLER SYSTEM.
  
  
  
 2) SHEET FP 00 - THE ARE INDICATIONS OF FIRE CODE
 REFERENCES; HOWEVER, NFPA 24 IS NOT.
  
 ALL UNDERGROUND SHALL COMPLY WITH:
  
 NFPA? 24 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE
 SERVICE MAINS AND THEIR APPURTENANCES, 2013 EDITION
  
 PER # 1 ABOVE IF THIS PERMIT IS INTENDED FOR
 UNDERGROUND, PROVIDE AN APPLICABLE NOTE OF COMPLIANCE.
  
  
  
  
 3) SHEET FP 00 - THE FIRE HYDRANT IS INDICATED AS BEING
 150' FROM THE FDC.
  
 PER NFPA 14
  
 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED
 NOT
 MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE HYDRANT
 CONNECTED
 TO AN APPROVED WATER SUPPLY.
  
 PLEASE CORRECT OR PROVIDE JUSTIFICATION TO INCREASE
 THIS DISTANCE.
  
  
  
 4) THERE ARE INDICATIONS OF NO SPRINKLERS IN THE DORM
 ROOM BATHROOMS AND CLOSETS.
  
 PER NFPA 13
  
 8.15.8 DWELLING UNITS.
 8.15.8.1 BATHROOMS.
 8.15.8.1.1* SPRINKLERS SHALL NOT BE REQUIRED IN
 BATHROOMS THAT
 ARE LOCATED WITHIN DWELLING UNITS OF HOTELS AND MOTELS,
 THAT DO
 NOT EXCEED 55 FT2 (5.1 M2) IN AREA, AND THAT HAVE WALLS
 AND
 CEILINGS OF NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE
 MATERIALS
 WITH A 15-MINUTE THERMAL BARRIER RATING, INCLUDING THE
 WALLS
 AND CEILINGS BEHIND ANY SHOWER ENCLOSURE OR TUB.
 8.15.8.2* CLOSETS AND PANTRIES. SPRINKLERS ARE NOT
 REQUIRED IN
 CLOTHES CLOSETS, LINEN CLOSETS, AND PANTRIES WITHIN
 DWELLING
 UNITS IN HOTELS AND MOTELS WHERE THE AREA OF THE SPACE
 DOES NOT
 EXCEED 24 FT2 (2.2 M2), THE LEAST DIMENSION DOES NOT
 EXCEED
 3 FT (0.9 M), AND THE WALLS AND CEILINGS ARE SURFACED
 WITH NONCOMBUSTIBLE
 OR LIMITED-COMBUSTIBLE MATERIALS.
  
 THE CODE DOES NOT EXEMPT PROTECTION OF THESE AREAS IN
 DORMITORIES.
  
 PLEASE REVIEW AND CORRECT.
  
  
  
 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
  
 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  


Account Summary | Usage Policy | Privacy Policy