2019-08-22 13:24:57 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE |
| MARSHAL, WITH THE FOLLOWING COMMENTS: |
| |
| |
| |
| 1) THERE IS INDICATIONS OF UNDERGROUND WORK. |
| |
| PLEASE CLARIFY IF THIS PERMIT IS INTENDED TO COVER ALL |
| UNDERGROUND WORK AS WELL AS FOR THE ABOVE GROUND |
| SPRINKLER SYSTEM. |
| |
| |
| |
| 2) SHEET FP 00 - THE ARE INDICATIONS OF FIRE CODE |
| REFERENCES; HOWEVER, NFPA 24 IS NOT. |
| |
| ALL UNDERGROUND SHALL COMPLY WITH: |
| |
| NFPA? 24 STANDARD FOR THE INSTALLATION OF PRIVATE FIRE |
| SERVICE MAINS AND THEIR APPURTENANCES, 2013 EDITION |
| |
| PER # 1 ABOVE IF THIS PERMIT IS INTENDED FOR |
| UNDERGROUND, PROVIDE AN APPLICABLE NOTE OF COMPLIANCE. |
| |
| |
| |
| |
| 3) SHEET FP 00 - THE FIRE HYDRANT IS INDICATED AS BEING |
| 150' FROM THE FDC. |
| |
| PER NFPA 14 |
| |
| 6.4.5.4* FIRE DEPARTMENT CONNECTIONS SHALL BE LOCATED |
| NOT |
| MORE THAN 100 FT (30.5 M) FROM THE NEAREST FIRE HYDRANT |
| CONNECTED |
| TO AN APPROVED WATER SUPPLY. |
| |
| PLEASE CORRECT OR PROVIDE JUSTIFICATION TO INCREASE |
| THIS DISTANCE. |
| |
| |
| |
| 4) THERE ARE INDICATIONS OF NO SPRINKLERS IN THE DORM |
| ROOM BATHROOMS AND CLOSETS. |
| |
| PER NFPA 13 |
| |
| 8.15.8 DWELLING UNITS. |
| 8.15.8.1 BATHROOMS. |
| 8.15.8.1.1* SPRINKLERS SHALL NOT BE REQUIRED IN |
| BATHROOMS THAT |
| ARE LOCATED WITHIN DWELLING UNITS OF HOTELS AND MOTELS, |
| THAT DO |
| NOT EXCEED 55 FT2 (5.1 M2) IN AREA, AND THAT HAVE WALLS |
| AND |
| CEILINGS OF NONCOMBUSTIBLE OR LIMITED-COMBUSTIBLE |
| MATERIALS |
| WITH A 15-MINUTE THERMAL BARRIER RATING, INCLUDING THE |
| WALLS |
| AND CEILINGS BEHIND ANY SHOWER ENCLOSURE OR TUB. |
| 8.15.8.2* CLOSETS AND PANTRIES. SPRINKLERS ARE NOT |
| REQUIRED IN |
| CLOTHES CLOSETS, LINEN CLOSETS, AND PANTRIES WITHIN |
| DWELLING |
| UNITS IN HOTELS AND MOTELS WHERE THE AREA OF THE SPACE |
| DOES NOT |
| EXCEED 24 FT2 (2.2 M2), THE LEAST DIMENSION DOES NOT |
| EXCEED |
| 3 FT (0.9 M), AND THE WALLS AND CEILINGS ARE SURFACED |
| WITH NONCOMBUSTIBLE |
| OR LIMITED-COMBUSTIBLE MATERIALS. |
| |
| THE CODE DOES NOT EXEMPT PROTECTION OF THESE AREAS IN |
| DORMITORIES. |
| |
| PLEASE REVIEW AND CORRECT. |
| |
| |
| |
| 5) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET |
| REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE |
| ABOVE. |
| |
| |
| |
| 6) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE |
| RE-SUBMITTAL OF THE ABOVE. |
| |
| |
| |
| |