| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| RE E3606.3 |
| 2. PROVIDE DETAILS ON PLAN OF GROUNDING ELECTRODE |
| SYSTEM AND WIRING. NEC 250.32; FBC RE E3607.3 |
| 3. EACH SHEET OF PLAN SHOULD STATE THE ADDRESS OF THE |
| WORK TO BE PERFORMED. WPB FBC 107.2.1 |
| 4. THE CONDUIT FROM THE METER CAN TO THE FIRST MEANS OF |
| DISCONNECT SHOULD NOT CONTAIN AN EQUIPMENT GROUNDING |
| CONDUCTOR. PROVIDE CORRECTION. NEC 250.6, 250.20, |
| 250.24 |
| 5. PROVIDE FLOOR PLAN SHOWING LOCATION OF SERVICE |
| EQUIPMENT AND ELECTRICAL PANELS. WPB FBC 107.2.1 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |