2019-10-03 09:33:34PLAN
 REVIEW COMMENTS
  
 2ND REVIEW: FBC SIXTH EDITION (2017)
 ROBERT MCDOUGAL, CBO
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561) 805-6714
 [email protected]
  
 DENIED BY BUILDING
 PLEASE ADDRESS THE ITEMS NOTED BELOW:
  
 1) FBC ACCESSIBILITY SECTION 202.4 ALTERATIONS
 AFFECTING PRIMARY FUNCTION AREAS. DOOR #10 BETWEEN
 CORRIDOR 811 AND 810 IS REQUIRED TO HAVE 18 INCHES AT
 THE LATCH ON THE PULL SIDE OF THE DOOR. SEE SECTION
 404.2.4.1 FOR A FRONT APPROACH TO THE PULL SIDE OF A
 SWING DOOR. ANOTHER OPTION WOULD BE TO REMOVE THIS DOOR
 AND CREATE A CASED OPENING.
  
 2) WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A
 RESPONSE LETTER ADDRESSING EACH ITEM ALONG WITH THE
 CITY RE-SUBMITTAL FORM.
  