2019-09-06 11:15:29 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. PER THE WPB AMENDMENTS TO THE FBC, PLAN (EACH SHEET |
| OF BOTH COPIES) IS REQUIRED TO BEAR THE NAME AND BE |
| SIGNED AND SEALED BY THE PERSON RESPONSIBLE FOR THE |
| DESIGN. THIS PERSON MUST BE A LICENSED DESIGN |
| PROFESSIONAL OR THE ELECTRICAL CONTRACTOR QUALIFIER. |
| PROVIDE CORRECTION. WPB FBC 107.1, 107.2; FS 471, 481 |
| 2. A GFCI PROTECTED RECEPTACLE OUTLET ON A 20 AMP |
| CIRCUIT IS REQUIRED WITHIN 3 FEET OF EACH BASIN. IF |
| THESE ARE EXISTING, SHOW AS EXISTING. IF NOT EXISTING, |
| PROVIDE PER CODE. THE RECEPTACLE OUTLET SHALL BE |
| LOCATED ON A WALL OR PARTITION THAT IS ADJACENT TO THE |
| BASIN OR BASIN COUNTERTOP, LOCATED ON THE COUNTERTOP, |
| OR INSTALLED ON THE SIDE OR FACE OF THE BASIN CABINET. |
| PROVIDE CORRECTION. NEC 210.11(C)(3), 210.52(D) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |