2019-09-13 10:56:10 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. REVISION SHOWS TWO 150 AMP FEEDS FROM A PANEL THAT |
| IS NOT IDENTIFIED. WHERE IS THIS PANEL LOCATED, WHAT IS |
| THE DISTANCE OF THE FEEDERS? PROVIDE VOLTAGE DROP |
| CALCULATIONS TO COMPLY WITH CODE. FBC EC C405.6.3; WPB |
| FBC 107.2.1 |
| 2. PROVIDE ACCURATE LOAD CALCULATION FOR EXISTING |
| PANEL, INCLUDE EXISTING AND NEW LOADS TO CONFIRM |
| CAPACITY OF SERVICE IS ADEQUATE. NEC 215.2, 220, 408.30 |
| 3. FEED FROM EXISTING PANEL TO PANELS SHOULD INCLUDE AN |
| EQUIPMENT GROUNDING CONDUCTOR. PROVIDE CORRECTION. NEC |
| 250.32(B), 250.118 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |