Date |
Text |
2019-10-22 11:19:55 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW |
| CHECKLIST. |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| ORIGINAL COMMENT: |
| 1- HOUSE VALUE IS MORE THAN $300.000. NEED TO COMPLY |
| WITH THE ROOF TO WALL CONNECTIONS AS REQUIRED BY SEC. |
| 706.8 FBC-EXISTING-BUILDING. |
| SEC. 706.8: |
| WHEN A ROOF COVERING ON AN EXISTING SITE-BUILT |
| SINGLE-FAMILY RESIDENTIAL STRUCTURE IS REMOVED AND |
| REPLACED ON A BUILDING THAT IS LOCATED IN THE |
| WIND-BORNE DEBRIS REGION AS DEFINED IN THE FLORIDA |
| BUILDING CODE, BUILDING AND THAT HAS AN INSURED VALUE |
| OF $300,000 OR MORE OR, IF THE BUILDING IS UNINSURED OR |
| FOR WHICH DOCUMENTATION OF INSURED VALUE IS NOT |
| PRESENTED, HAS A JUST VALUATION FOR THE STRUCTURE FOR |
| PURPOSES OF AD VALOREM TAXATION OF $300,000 OR MORE: |
| (A)ROOF TO WALL CONNECTIONS SHALL BE IMPROVED AS |
| REQUIRED BY SECTION 706.8.1. |
| (B)MANDATED RETROFITS OF THE ROOF-TO-WALL CONNECTION |
| SHALL NOT BE REQUIRED BEYOND A 15 PERCENT INCREASE IN |
| THE COST OF REROOFING. |
| EXCEPTION: SINGLE-FAMILY RESIDENTIAL STRUCTURES |
| PERMITTED SUBJECT TO THE FLORIDA BUILDING CODE ARE NOT |
| REQUIRED TO COMPLY WITH THIS SECTION. |
| |
| RESPONSE: |
| CONTRACTOR SUBMITTED PALM BEACH COUNTY FORM 200 SIGNED |
| BY JOSEPH PISCIOTTI (BUILDING CONTRACTOR). THE |
| INFORMATION SHOWN ON THE FORM DOESN'T COMPLY WITH THE |
| REQUIREMENTS OF SEC. 706.8.1 FBC-EXISTING BUILDING. |
| THIS IS NOT AN ENGINEERED DESIGN OR INFORMATION |
| SUBMITTED DOESN'T COMPLY WITH THE PRESCRIPTIVE RETROFIT |
| SOLUTIONS PROVIDED IN SEC. 706.8.1.1. THE |
| SPECIFICATIONS FOR THE STRAP ARE INCOMPLETE. CONTRACTOR |
| HIMSELF SPECIFIES THAT THE ADDITIONAL FASTENERS IN THE |
| EXISTING ANCHORS DON'T PROVIDE COMPLIANCE. IN ADDITION, |
| CONTRACTOR SPECIFIED THAT THERE ARE NO EXISTING ANCHORS |
| AND FASTENERS AT THE LOCATIONS PROPOSED FOR MITIGATION |
| RETROFIT. EXTERIOR WALLS ARE WOOD, NOT CBC. THE ROOF |
| GEOMETRY IS GABLE AND THERE IS A FLAT ROOF ALSO. THERE |
| IS NOT ADDRESS IDENTIFYING THE HOUSE. |
| NEED TO PROVIDE AND ENGINEERED DESIGN OR PROVIDE |
| PRESCRIPTIVE DESIGN. SEC. 706.8.1 FBC-RESIDENTIAL. |
| |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |