2019-08-27 08:41:01 | RESIDENTIAL (R3) RE-ROOF SECOND BUILDING REVIEW | | CHECKLIST. | | CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. | | | | 1- SCOPE OF WORK IS NOT CLEAR. PERMIT APPLICATION CALLS | | FOR REPLACEMENT OF 5 SQUARES OF ROOF TILE. NOW, | | CONTRACTOR SUBMITTED PLANS FOR AN ADDITION TO THE | | HOUSE. THE ADDITION IS ALREADY APPROVED. CLARIFY IF THE | | ROOFING WORK IS FOR THE ADDITION AS SHOWN ON PLANS. IF | | THIS IS FOR THE ADDITION, THEN THIS IS A ROOFING | | SUB-PERMIT FOR THE ADDITION MASTER #19021315 NOT A | | RE-ROOF PERMIT. CLARIFY AND REVISE SCOPE OF WORK AS | | REQUIRED ON THE PERMIT APPLICATION. SEC. 107.2.1 CITY | | AMENDMENTS. | | | | 2- ROOF TILE NOA 18-0829.03 SUBMITTED: CLEARLY MARK | | ROOF TILE FASTENING METHOD AS REQUIRED BY CITY POLICY | | FOR ALL ROOFING PERMITS. IF USING SCREWS, THEN CLEARLY | | MARK THE NUMBER AND SIZE OF SCREWS. IF USING FOAM | | ADHESIVE, THEN CLEARLY MARK PADDY SIZE. SEC. 107.2.1 | | CITY AMENDMENTS. | | | | 3- PROVIDE PRODUCT APPROVAL FOR ROOF TILE ADHESIVE IF | | THIS IS THE ROOF TILE FASTENING METHOD SPECIFIED | | ON-ITEM #3 ABOVE. AND, CLEARLY MARK PADDY SIZE. SEC. | | 61G20-3.001 FAC. | | | | IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE | | TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE | | COMMENTS, | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | BUILDING DIVISION | | (561)805-6712 | | [email protected] | | |
|