2019-08-19 09:41:48 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS |
| CODE: FBC 6TH EDITION (2017) AND CITY AMENDMENTS. |
| |
| 1- PERMIT APPLICATION CALLS FOR REPLACEMENT OF 5 |
| SQUARES OF ROOF TILE. NEED TO RE-ROOF ENTIRE ROOF AS |
| REQUIRED BY SEC. 706.1.1 FBC-EXISTING BUILDING. NO MORE |
| THAN 25% OF THE ROOF OF THE TOTAL ROOF AREA SHALL BE |
| REPLACED UNLESS ENTIRE EXISTING ROOF IS REPLACED. |
| REVISE DESCRIPTION IN-PERMIT APPLICATION. |
| |
| 2- ROOF TILE NOA 02-0415.05 EXPIRED ON 05/23/07. NEED |
| TO PROVIDE CURRENT PRODUCT APPROVAL (2 COPIES) AS |
| REQUIRED BY SEC. 61G20-3.001 FAC. |
| |
| 3- - ROOF TILE NOA 18-0119.03 SUBMITTED: CLEARLY MARK |
| ROOF TILE FASTENING METHOD AS REQUIRED BY CITY POLICY |
| FOR ALL ROOFING PERMITS. IF USING SCREWS, THEN CLEARLY |
| MARK THE NUMBER AND SIZE OF SCREWS. IF USING FOAM |
| ADHESIVE, THEN CLEARLY MARK PADDY SIZE. |
| |
| 4- PROVIDE PRODUCT APPROVAL FOR ROOF TILE ADHESIVE IF |
| THIS IS THE ROOF TILE FASTENING METHOD SPECIFIED |
| ON-ITEM #3 ABOVE. AND, CLEARLY MARK PADDY SIZE. SEC. |
| 61G20-3.001 FAC. |
| |
| 5- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS, |
| CONTRACTOR'S OVERHEAD AND PROFIT AS REQUIRED BY SEC. |
| 109.3 CITY AMENDMENTS. PROVIDE TOTAL ROOF SQUARE FEET |
| FOR PROPER VALUATION AS REQUIRED BY CITY POLICY FOR ALL |
| ROOFING PERMITS. |
| |
| 6- NEED RECORDED NOTICE OF COMMENCEMENT. SEC. 717.13 |
| F.S. |
| |
| IN ORDER TO AVOID MULTIPLE SUBMITTAL, PLEASE FEEL FREE |
| TO CONTACT ME IF YOU HAVE ANY QUESTIONS REGARDING THESE |
| COMMENTS, |