Date |
Text |
2019-09-12 17:07:08 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19080808 |
| 9/12/19 |
| |
| CODES IN EFFECT: |
| |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE PROPOSED PROJECT HAS BEEN IDENTIFIED AS A CHANGE |
| OF OCCUPANCY ACCORDING TO THE BUILDING REVIEW COMMENTS. |
| PLEASE REFER TO SECTION1009.1 FBC EX AND PROVIDE |
| MINIMUM VENTILATION CALCULATIONS FOR ALL ROOMS AND |
| SPACES IN ACCORDANCE WITH TABLE 403.3.1.1 FBC M. |
| PROVIDE A SCHEDULE ON THE PLAN THAT INDICATES BOTH THE |
| REQUIRED AND THE "TO BE REQUIRED" CFMS OF OUTDOOR |
| VENTILATION AIR. |
| |
| 2) THERE ARE NO MECHANICAL PLANS FOR THE PROPOSED |
| PROJECT HOWEVER THE ARCHITECTURAL PLAN IS INDICATING AC |
| SYSTEMS AND AN EXHAUST FAN IN THE NEW GARAGE. PLEASE |
| PROVIDE MECHANICAL PLANS THAT CLARIFY IF THE AC SYSTEMS |
| ARE NEW OR EXISTING, AND THAT SHOW ALL REQUIIRED |
| ALTERATIONS TO THE EXISTING DUCTWORK TO ACCOMODATE THE |
| CHANGE OF OCCUPANCY AND THE NEW ROOMS AND SPACES. |
| |
| 3) PROVIDE EXHAUST VENTILATION CALCULATIONS FOR THE |
| GARAGE AND AN EXHAUST FAN SCHEDULE- SEE TABLE 403.3.1.1 |
| FOR REQUIRED VENTILATION RATE, AND PROVIDE A SEQUENCE |
| OF OPERATION FOR THE FAN ON THE PLAN. |
| |
| 4) THE NEW FAN OPENING IN THE EXTERIOR WALL SHALL BE |
| IMPACT PROTECTED AND WIND RESISTANT IN ACCORDANCE WITH |
| RULE 9N-03 FAC. PLEASE PROVIDE A MIAMI DADE NOA OR A |
| FLORIDA PRODUCT APPROVAL FOR THE FAN OR FOR A LOUVER TO |
| COVER THE FAN OPENING. |
| |
| 5) THE NEW BATHROOM SHALL BE MECHANICALLY VENITLATED IN |
| ACCORDANCE WITH SECTION SECTION 1203.5.2.1 FBC B. |
| PLEASE PROVIDE AN EXHAUST VENTILATION PLAN IN |
| COMPLIANCE WITH TABLE 403.3.1.1 FBC M. |
| |
| 6) THE NEW KITCHEN SHALL HAVE AN EXHAUST VENTILATION |
| SYSTEM SIZED AT A RATE OF 100 CFMS INTERMITTENT OR 25 |
| CFMS CONTINUOUS. PLEASE INDICATE HOW COMPLIANCE WILL BE |
| MET. |
| |
| 7) PROVIDE AN ENLARGED KITCHEN PLAN AND EQUIPMENT |
| SCHEDULE- SECTION 107.2.1 FBC M. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 401 CLEMATIS STREET |
| WEST PALM BEACH FL 33401 |
| 561-805-6719 |
| [email protected] |
| |
| |