Date |
Text |
2019-09-07 09:35:23 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19080808 |
| ADD: 314 FLAMINGO DRIVE |
| CONT: PEDRO FURTADO |
| TEL: 818-620-7860 |
| E-MAIL: DAMONMONTYDMAC.COM |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 1ST REVIEW |
| DATE: SAT. SEPT. 07/2019 |
| ACTION: DENIED |
| |
| 1) SHEET A1.01 MISSING INFORMATION. 2017 WEST PALM |
| BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER |
| 1, ADMINISTRATIVE CODE, 107.3.5 MINIMUM PLAN REVIEW |
| CRITERIA FOR BUILDINGS. |
| 107.3.5.1 COMMERCIAL BUILDINGS: |
| 107.3.5.1.1 BUILDING |
| UNDER WHICH BUILDING CODE WERE THE PLANS DEVELOPED |
| SITE REQUIREMENTS: |
| PARKING |
| DRIVING/TURNING RADIUS |
| FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV) |
| SET BACK/SEPARATION |
| WATER LINES AND SEWER LINES |
| OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS |
| SHALL BE DETERMINED CHAPTER 4 FBC-B |
| MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED, NO |
| SQ. FOOTAGE OF OCCUPANCIES ON PLANS, |
| NOR TOTAL SQUARE FOOTAGE |
| RATING OF FIRE BARRIER ASSEMBLIES, VERTICAL AND |
| HORIZONTAL |
| BUILDING FIRE SPRINKLERED OR NOT, FIRE SPRINKLER PLANS |
| OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE: |
| OCCUPANCY LOAD |
| GROSS |
| NET |
| MEANS OF EGRESS |
| EXIT ACCESS |
| EXIT |
| EXIT DISCHARGE |
| STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION |
| DOORS |
| EMERGENCY LIGHTING AND EXIT SIGNS |
| ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING: |
| SITE REQUIREMENTS/ ACCESSIBLE ROUTE |
| TOILET AND BATHING FACILITIES/ KITCHENETTE |
| DRINKING FOUNTAINS |
| |
| 2) THE DESIGNER OF RECORD HAS NOT DISCLOSED UNDER WHAT |
| BUILDING CODE THESE PLANS WERE DEVELOPED. STATEWIDE THE |
| 2017 FAMILY OF FLORIDA BUILDING CODES WERE ADOPTED ON |
| DEC. 31/ 2017. UPDATE PLANS. |
| |
| 3) THE DESIGNER OF RECORD HAS NOT DISCLOSED UNDER THE |
| 2017 FLORIDA EXISTING BUILDING CODE WHAT METHOD THE |
| PLANS WERE DEVELOPED. FOR THIS REVIEW THE REVIEWER WILL |
| BE USING BOTH THE 2017 FBC-B AND THE 2017 EXIST. |
| BUILDING CODE CHAPTER 10 CHANGE OF OCCUPANCY SECTION |
| 1001.2.2. CHANGE OF OCCUPANCY CLASSIFICATION OR GROUP. |
| WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING |
| CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012 |
| SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY |
| CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN |
| OCCUPANCY CLASSIFICATION. |
| |
| THIS BUILDING WE COULD NOT FIND A BUSINESS TAX RECEIPT |
| / BUT PALM BEACH COUNTY PROPERTY APPRAISERS HAS THE |
| OCCUPANCY TYPE LISTED AS WAREHOUSE/ STORAGE. THAT IS |
| WHY WE ARE LISTING THIS REVIEW AS A CHANGE IN |
| OCCUPANCY/ CHANGE IN USE. |
| |
| 4A) PLEASE SHOW COMPLIANCE WITH THE 2017 EXIST. BUILD. |
| CODE SECTION 1002.1 COMPLIANCE WITH THE BUILDING CODE. |
| WHERE THE CHARACTER OR USE OF AN EXISTING BUILDING OR |
| PART OF AN EXISTING BUILDING IS CHANGED TO ONE OF THE |
| FOLLOWING SPECIAL USE OR OCCUPANCY CATEGORIES AS |
| DEFINED IN THE FLORIDA BUILDING CODE, BUILDING, THE |
| BUILDING SHALL COMPLY WITH ALL OF THE APPLICABLE |
| REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING: |
| 406.3.MOTOR VEHICLE-RELATED OCCUPANCIES. |
| EXIST BLDG. CODE 406.4.6 MIXED OCCUPANCY SEPARATION. |
| PARKING GARAGES SHALL BE SEPARATED FROM OTHER |
| OCCUPANCIES IN ACCORDANCE WITH SECTION 508.1 OF THE |
| FBC-B. WHERE A BUILDING CONTAINS MORE THAN ONE |
| OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF SHALL |
| COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION 508.2, |
| 508.3 OR 508.4, OR A COMBINATION OF THESE SECTIONS. |
| PLEASE NOTE PARKING GARAGES ARE PART OF THE SPECIALTY |
| OCCUPANCIES FOUND IN CHAPTER 4 AND WILL REQUIRE FIRE |
| SEPARATION AS PER TABLE 508.4 OF THE FBC-B. PLEASE ALSO |
| NOTE FOOTNOTE B. THE REQUIRED SEPARATION FROM AREAS |
| USED ONLY FOR PRIVATE OR PLEASURE VEHICLES SHALL BE |
| REDUCED BY 1 HOUR BUT NOT LESS THAN 1 HOUR. OPENING |
| PROTECTIVES FOR DOORS CAN BE FOUND UNDER THE FBC-B |
| TABLE 716.5. PRIVATE GARAGES UNDER 1,000 SQ. IS TO BE |
| CONSIDERED AN U OCCUPANCY (UTILITY). IN THE 2017 FBC-B |
| 406.3.1 THE CLASSIFICATION FOR A PRIVATE GARAGE AS |
| UTILITY STILL REQUIRES A 1 HOUR FIRE BARRIER IN |
| COMPLIANCE WITH SECTION 707 OF THE FBC-B. |
| |
| 4B) PLEASE NOTE THAT PRIVATE GARAGES NEED ONLY TO |
| COMPLY WITH 406.3.1 THROUGH 406.3.6. VENTILATION |
| REQUIREMENTS FOUND UNDER 406.6.2 ARE NOT REQUIRED! |
| |
| 5A) THE IDEA OF CALLING THIS STRUCTURE A LIVE/ WORK |
| UNIT DOES NOT MEET THE CRITERIA FOUND IN SECTION |
| 419.1.1 LIMITATIONS OF THE 2017 FBC-B. THE |
| NON-RESIDENTIAL AREA IS PERMITTED TO BE NOT GREATER |
| THAN50 % OF THE AREA OF EACH LIVE/ WORK UNITS. |
| |
| 5B) THE OTHER OCCUPANCY SEPARATION THAT WILL NEED TO |
| OCCUR IS THE RESIDENTIAL R-3 VERSES THE A-3 OCCUPANCY |
| (GALLERY). TABLE 508.4 OF THE 2017 FBC-B WILL ALSO |
| REQUIRE A 1 HOUR FIRE SEPARATION PER TABLE 508.4 FOR A |
| SPRINKLERED BUILDING. |
| |
| 6) THE OCCUPANCY TYPE HAD NOT BEEN DECLARED BUT WITH AN |
| AREA OF 1,250 S. F. / 30= 42 OCC. FOR THE GALLERY, |
| LIBRARY 344 S. F. / 30= 12 OCC. AND STORAGE 236 S. F. / |
| 300= 1 OCC. FOR A TOTAL OF 50 OCCUPANTS. THIS WOULD |
| REQUIRE 2 EGRESS DOORS, BOTH THE GALLERY AND LIBRARY |
| DOORS CAN SERVE THIS PURPOSE BUT WILL NEED TO SHOW EXIT |
| LIGHTS OVER THESE DOORS IN COMPLIANCE WITH THE 2017 |
| FBC-B SECTION 1108.2. PLEASE ALSO DEVELOP A LIFE SAFETY |
| PLAN SHOWING MEANS OF EGRESS, COMMON PATH OF TRAVEL, |
| AND OCCUPANT LOADS ON THE LIFE SAFETY PLAN. |
| |
| 7) IN THE 2017 EXIST. FBC SHOW COMPLIANCE WITH SECTIONS |
| 1012.2 FIRE PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS |
| SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS 1012.2.1 |
| AND 1012.2.2. |
| |
| |
| 7A) EXIST. BUILD. CODE 1012.2.1 FIRE SPRINKLER SYSTEM. |
| WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS OR |
| WHERE THERE IS A CHANGE OF OCCUPANCY WITHIN A SPACE |
| WHERE THERE IS A DIFFERENT FIRE PROTECTION SYSTEM |
| THRESHOLD REQUIREMENT IN CHAPTER 9 OF THE FLORIDA |
| BUILDING CODE, BUILDING THAT REQUIRES AN AUTOMATIC FIRE |
| SPRINKLER SYSTEM TO BE PROVIDED BASED ON THE NEW |
| OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA |
| BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE PROVIDED |
| THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY |
| OCCURS. |
| |
| |
| 7B) EXIST. BUILD. CODE 1012.2.2 FIRE ALARM AND |
| DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY |
| CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF |
| OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT |
| FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER |
| 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES |
| A FIRE ALARM AND DETECTION SYSTEM TO BE PROVIDED BASED |
| ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF |
| THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL |
| BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION |
| APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT |
| THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A |
| FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL |
| BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF |
| OCCUPANCY OCCURS IN ACCORDANCE WITH SECTION 907 OF THE |
| FLORIDA BUILDING CODE, BUILDING AS REQUIRED FOR NEW |
| CONSTRUCTION. |
| |
| 8) PLEASE SHOW HOW COMPLIANCE WITH THE 2017 EXIST. |
| BUILD. CODE SECTION 1012.1.4 WILL BE ACHIEVED. 1012.1.4 |
| ACCESSIBILITY. ALL BUILDINGS UNDERGOING A CHANGE OF |
| OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION |
| 1012.8. 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT |
| UNDERGO A CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION |
| SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA |
| BUILDING CODE, ACCESSIBILITY. |
| NOTICE: 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. |
| ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND |
| SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE |
| FLORIDA BUILDING CODE, BUILDING. |
| |
| 8A) WHEN STRUCTURES ARE ALTERED, AND OR GO THROUGH A |
| CHANGE OF OCCUPANCY THE BUILDING IS LOOKED AT FOR |
| ACCESSIBILITY ISSUES. NEW CONSTRUCTION ELEMENTS HAVE TO |
| COMPLY WITH ACCESSIBILITY. EXISTING ELEMENTS THAT DO |
| NOT COMPLY ONLY 20 % OF THE CONTRACT VALUE (THAT MAY |
| INCREASE DEALING WITH CODE ISSUES THAT HAVE TO BE |
| BROUGHT UP TO CODE). THE PLANS WERE SUBMITTED WITH A |
| CONSTRUCTION VALUE OF $75,000 DOLLARS OF VALUE, TO |
| BRING ACCESSIBLE ELEMENTS UP TO CODE UP TO AN |
| ADDITIONAL $15,000.00 MAY HAVE TO BE SPENT AND IN THIS |
| ORDER. |
| 2017 FBC- ACCESS. CODE. 202.4.2 ACCESSIBLE FEATURES IN |
| THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF |
| ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE |
| ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO |
| THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL |
| SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE |
| MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE |
| COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO |
| PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS |
| THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING |
| ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE |
| ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE |
| ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX |
| RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE |
| DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL |
| ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND |
| ALARMS. |
| |
| EITHER THE DESIGNER OF RECORD OR CONTRACTOR ON THEIR |
| LETTERHEAD CAN SUBMIT A BREAK DOWN WHERE THESE FUNDS |
| ARE TO BE SPENT IN THE CASE ALL OF THE ACCESSIBLE |
| ELEMENTS CANNOT BE FIXED WITH THE STATED DOLLAR AMOUNT |
| GIVEN. THE REMAINDER OF THE ACCESSIBLE ELEMENTS THAT |
| WERE NOT CORRECTED CAN BE LEFT AS IS, THE |
| DISPROPORTIONALITY HAS BEEN MET. |
| |
| 8B) THE PLANS WILL NEED TO SHOW THAT THERE IS AN |
| ACCESSIBLE ENTRANCE AND BECAUSE THE REQUIREMENT FOR 2 |
| EXITS BOTH DOORS FROM THE GALLERY/ LIBRARY WILL NEED TO |
| SHOW THEY ARE AT GRADE AND ACCESSIBLE. |
| |
| 2 ACCESSIBLE MEANS OF EGRESS REQUIRED. 2017 |
| FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS |
| SHALL COMPLY WITH SECTION 1003.2.13 OF THE |
| INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001 |
| SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL |
| BUILDING CODE (2003 EDITION). |
| |
| 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS |
| IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY |
| ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE |
| SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS. |
| |
| 8C) PLEASE NOTE THE SHEET A1.01 DOES NOT SHOW |
| RESTROOMS, DRINKING FOUNTAINS NOR A SERVICE SINK IN THE |
| GALLERY / LIBRARY OCCUPANCY. THE FLOOR PLAN A1.01 DOES |
| NOT SHOW ANY RESTROOMS WITHIN THE GALLERY / LIBRARY |
| OCCUPANCY. PLEASE PROVIDE THE OCCUPANT LOAD AND |
| COMPLIANCE WITH THE 2017 FBC-EXIST. BUILD. 1010.1 |
| REVIEW 1010.6 AND IN THE 2017 FBC-B SECTIONS 2902.1.1, |
| 2902.2 AND TABLE 2902.1 TO SHOW ACCESSIBLE DRINKING |
| FOUNTAINS & RESTROOMS. |
| |
| 8D) THE FLOORPLAN FOR THE RESIDENTIAL UNIT SHOWS A |
| RESTROOM, WATERCLOSET AND LAV ONLY PLEASE SHOW WHAT |
| SIZE THE POCKET DOOR IS TO THE RESTROOM. 2017 |
| ACCESSIBILITY CODE 233.3.6 IF ONLY A TOILET ROOM IS |
| PROVIDED AT GRADE LEVEL, SUCH TOILET ROOM SHALL HAVE A |
| CLEAR OPENING OF 29 INCHES. |
| |
| 8E) THE FLOOR PLAN A1.1 DOES NOT SHOW A DRINKING |
| FOUNTAIN. PLEASE PROVIDE COMPLIANCE WITH 2017 FBC- |
| ACCESS. CODE SECTION 211.2 MINIMUM NUMBER. |
| NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED. |
| ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH |
| 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH |
| 602.7. |
| EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES |
| WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE |
| PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING |
| FOUNTAINS. |
| |
| 9) THE FLOOR PLAN A.1.1. SHOWS IN THE R-3 OCCUPANCY A 2 |
| STORY UNIT WITH ENCLOSED STAIRWAY ON THE 1ST FLOOR |
| LEADING DIRECTLY TO THE EXTERIOR. WHAT THE PLAN DOES |
| NOT INDICATE IF THE STAIRWAY IS 1 HOUR FIRE RATED |
| WALLS? |
| PLEASE PROVIDE OF WHAT MATERIALS THE STAIRWELL WALLS |
| ARE MADE OF? 2017 EXIST. BUILD. CODE: |
| 1012.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD |
| CATEGORY. |
| |
| WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A |
| HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE |
| 1012.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE |
| REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING |
| CODE, BUILDING. |
| EXCEPTION 4 DEALS WITH RATED CORRIDOR WALLS BUT THE |
| SAME CAN BE USED FOR STAIRWELL WALLS. THE OTHER ISSUE |
| IS UNDER THE STAIRWELL THE PLANS SHOW A RESTROOM AND |
| WASHER/ DRYER ROOM. WHAT ARE THESE WALLS AND CEILING |
| MADE OF? |
| EXCEPTIONS: |
| 4. EXISTING CORRIDOR WALLS CONSTRUCTED ON BOTH SIDES OF |
| WOOD LATH AND PLASTER IN GOOD CONDITION OR 1/2- |
| INCH-THICK (12.7 MM) GYPSUM WALLBOARD SHALL BE |
| PERMITTED. SUCH WALLS SHALL EITHER TERMINATE AT THE |
| UNDERSIDE OF A CEILING OF EQUIVALENT CONSTRUCTION OR |
| EXTEND TO THE UNDERSIDE OF THE FLOOR OR ROOF NEXT |
| ABOVE. |
| |
| 10) SHEET A.1.1 SHOWS A NEW STOREFRONT DOORS AND GARAGE |
| DOOR PLEASE PROVIDE COMPLIANCE WITH: |
| 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS, |
| 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT |
| OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005, |
| RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS |
| OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT |
| APPROVALS: |
| (31)(A) EXTERIOR DOORS ,OVERHEAD GARAGE DOOR |
| (B) WINDOWS AND MULLIONS (POSSIBLE SIDELIGHTS) |
| |
| 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE |
| PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF |
| RECORD AND BEFORE SUBMISSION TO THE BUILDING |
| DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE |
| IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING, |
| MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED |
| INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE |
| PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1 |
| INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN |
| ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS. |
| FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH |
| INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM |
| LOADS AND SPACING USED IN THE TESTS. |
| |
| 12) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE |
| PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03 |
| SHALL BE REVIEWED AND APPROVED IN WRITING BY THE |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR |
| JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE |
| ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING |
| ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC.. |
| |
| 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF |
| THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE |
| PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE |
| TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO |
| THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD. |
| DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR |
| APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED |
| DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST |
| THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS |
| FOR REVIEW BY THE BUILDING OFFICIAL. |
| |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| |
| 14) SHEET A1.1 WITH NEW EXTERIOR DOORS WE WILL NEED TO |
| HAVE THE WIND DESIGN CRITERIA. |
| 2017 FBC-B 1603.1.4 WIND DESIGN DATA. |
| THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL |
| BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE |
| DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE |
| STRUCTURE: |
| |
| 14.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND |
| GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED, |
| VASD, AS DETERMINED IN ACCORDANCE WITH SECTION |
| 1609.3.1. |
| |
| 14.2. RISK CATEGORY. |
| |
| 14.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE |
| THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2. |
| HEIGHT AND EXPOSURE. |
| |
| 14.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT. |
| |
| 14.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR |
| COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY |
| DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL |
| RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF. |
| TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT & |
| EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE |
| BUILDING. |
| 1609.3.1 WIND SPEED CONVERSION VULT TO VASD. |
| |
| 15) CITY AND COUNTY RECORDS INDICATE THIS STRUCTURE WAS |
| BUILT IN 1964 WHEN ASBESTOS WAS USED IN CONSTRUCTION. |
| IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO |
| ADVISE YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY |
| TO COMPLY WITH THE STATE & FEDERAL ASBESTOS |
| REGULATIONS, INCLUDING SECTION 376.60 F. S. AND CFR 61- |
| NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS |
| SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION TO THE |
| DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: * |
| DEMOLITION OF ALL REGULATED STRUCTURES; |
| * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES |
| WHERE ASBESTOS IS DISTURBED OR REMOVED. |
| NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY. |
| |
| FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT |
| THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING |
| HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT |
| (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR |
| POLLUTION CONTROL SECTION) |
| |
| 901 EVERNIA STREET |
| WEST PALM BEACH, FL 33401 |
| (561) 355-3070 |
| |
| 16) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW |
| BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON |
| APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO |
| THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND |
| WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE |
| PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO |
| THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT: |
| HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC |
| TFEES/FORMS/QUESTIONNAIRE.PDF |
| |
| 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE |
| REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES |
| AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 / FAX: 561-805-6676 |