Plan Review Notes
Plan Review Notes For Permit 19080808
Permit Number 19080808
Review Stop B
Sequence Number 1
Notes
Date Text
2019-09-07 09:35:232017 FBC- BUILDING PLAN REVIEW
 W. P. B. PERMIT: 19080808
 ADD: 314 FLAMINGO DRIVE
 CONT: PEDRO FURTADO
 TEL: 818-620-7860
 E-MAIL: DAMONMONTYDMAC.COM
  
 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION.
  
 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW
 CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES
 SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING.
  
 1ST REVIEW
 DATE: SAT. SEPT. 07/2019
 ACTION: DENIED
  
 1) SHEET A1.01 MISSING INFORMATION. 2017 WEST PALM
 BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER
 1, ADMINISTRATIVE CODE, 107.3.5 MINIMUM PLAN REVIEW
 CRITERIA FOR BUILDINGS.
 107.3.5.1 COMMERCIAL BUILDINGS:
 107.3.5.1.1 BUILDING
 UNDER WHICH BUILDING CODE WERE THE PLANS DEVELOPED
 SITE REQUIREMENTS:
 PARKING
 DRIVING/TURNING RADIUS
 FIRE HYDRANT/WATER SUPPLY/POST INDICATOR VALVE (PIV)
 SET BACK/SEPARATION
 WATER LINES AND SEWER LINES
 OCCUPANCY GROUP AND SPECIAL OCCUPANCY REQUIREMENTS
 SHALL BE DETERMINED CHAPTER 4 FBC-B
 MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED, NO
 SQ. FOOTAGE OF OCCUPANCIES ON PLANS,
 NOR TOTAL SQUARE FOOTAGE
 RATING OF FIRE BARRIER ASSEMBLIES, VERTICAL AND
 HORIZONTAL
 BUILDING FIRE SPRINKLERED OR NOT, FIRE SPRINKLER PLANS
 OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 STAIRS CONSTRUCTION/GEOMETRY AND PROTECTION
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 ACCESSIBILITY REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 SITE REQUIREMENTS/ ACCESSIBLE ROUTE
 TOILET AND BATHING FACILITIES/ KITCHENETTE
 DRINKING FOUNTAINS
  
 2) THE DESIGNER OF RECORD HAS NOT DISCLOSED UNDER WHAT
 BUILDING CODE THESE PLANS WERE DEVELOPED. STATEWIDE THE
 2017 FAMILY OF FLORIDA BUILDING CODES WERE ADOPTED ON
 DEC. 31/ 2017. UPDATE PLANS.
  
 3) THE DESIGNER OF RECORD HAS NOT DISCLOSED UNDER THE
 2017 FLORIDA EXISTING BUILDING CODE WHAT METHOD THE
 PLANS WERE DEVELOPED. FOR THIS REVIEW THE REVIEWER WILL
 BE USING BOTH THE 2017 FBC-B AND THE 2017 EXIST.
 BUILDING CODE CHAPTER 10 CHANGE OF OCCUPANCY SECTION
 1001.2.2. CHANGE OF OCCUPANCY CLASSIFICATION OR GROUP.
 WHERE THE OCCUPANCY CLASSIFICATION OF A BUILDING
 CHANGES, THE PROVISIONS OF SECTIONS 1002 THROUGH 1012
 SHALL APPLY. THIS INCLUDES A CHANGE OF OCCUPANCY
 CLASSIFICATION AND A CHANGE TO ANOTHER GROUP WITHIN AN
 OCCUPANCY CLASSIFICATION.
  
 THIS BUILDING WE COULD NOT FIND A BUSINESS TAX RECEIPT
 / BUT PALM BEACH COUNTY PROPERTY APPRAISERS HAS THE
 OCCUPANCY TYPE LISTED AS WAREHOUSE/ STORAGE. THAT IS
 WHY WE ARE LISTING THIS REVIEW AS A CHANGE IN
 OCCUPANCY/ CHANGE IN USE.
  
 4A) PLEASE SHOW COMPLIANCE WITH THE 2017 EXIST. BUILD.
 CODE SECTION 1002.1 COMPLIANCE WITH THE BUILDING CODE.
 WHERE THE CHARACTER OR USE OF AN EXISTING BUILDING OR
 PART OF AN EXISTING BUILDING IS CHANGED TO ONE OF THE
 FOLLOWING SPECIAL USE OR OCCUPANCY CATEGORIES AS
 DEFINED IN THE FLORIDA BUILDING CODE, BUILDING, THE
 BUILDING SHALL COMPLY WITH ALL OF THE APPLICABLE
 REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING:
 406.3.MOTOR VEHICLE-RELATED OCCUPANCIES.
 EXIST BLDG. CODE 406.4.6 MIXED OCCUPANCY SEPARATION.
 PARKING GARAGES SHALL BE SEPARATED FROM OTHER
 OCCUPANCIES IN ACCORDANCE WITH SECTION 508.1 OF THE
 FBC-B. WHERE A BUILDING CONTAINS MORE THAN ONE
 OCCUPANCY GROUP, THE BUILDING OR PORTION THEREOF SHALL
 COMPLY WITH THE APPLICABLE PROVISIONS OF SECTION 508.2,
 508.3 OR 508.4, OR A COMBINATION OF THESE SECTIONS.
 PLEASE NOTE PARKING GARAGES ARE PART OF THE SPECIALTY
 OCCUPANCIES FOUND IN CHAPTER 4 AND WILL REQUIRE FIRE
 SEPARATION AS PER TABLE 508.4 OF THE FBC-B. PLEASE ALSO
 NOTE FOOTNOTE B. THE REQUIRED SEPARATION FROM AREAS
 USED ONLY FOR PRIVATE OR PLEASURE VEHICLES SHALL BE
 REDUCED BY 1 HOUR BUT NOT LESS THAN 1 HOUR. OPENING
 PROTECTIVES FOR DOORS CAN BE FOUND UNDER THE FBC-B
 TABLE 716.5. PRIVATE GARAGES UNDER 1,000 SQ. IS TO BE
 CONSIDERED AN U OCCUPANCY (UTILITY). IN THE 2017 FBC-B
 406.3.1 THE CLASSIFICATION FOR A PRIVATE GARAGE AS
 UTILITY STILL REQUIRES A 1 HOUR FIRE BARRIER IN
 COMPLIANCE WITH SECTION 707 OF THE FBC-B.
  
 4B) PLEASE NOTE THAT PRIVATE GARAGES NEED ONLY TO
 COMPLY WITH 406.3.1 THROUGH 406.3.6. VENTILATION
 REQUIREMENTS FOUND UNDER 406.6.2 ARE NOT REQUIRED!
  
 5A) THE IDEA OF CALLING THIS STRUCTURE A LIVE/ WORK
 UNIT DOES NOT MEET THE CRITERIA FOUND IN SECTION
 419.1.1 LIMITATIONS OF THE 2017 FBC-B. THE
 NON-RESIDENTIAL AREA IS PERMITTED TO BE NOT GREATER
 THAN50 % OF THE AREA OF EACH LIVE/ WORK UNITS.
  
 5B) THE OTHER OCCUPANCY SEPARATION THAT WILL NEED TO
 OCCUR IS THE RESIDENTIAL R-3 VERSES THE A-3 OCCUPANCY
 (GALLERY). TABLE 508.4 OF THE 2017 FBC-B WILL ALSO
 REQUIRE A 1 HOUR FIRE SEPARATION PER TABLE 508.4 FOR A
 SPRINKLERED BUILDING.
  
 6) THE OCCUPANCY TYPE HAD NOT BEEN DECLARED BUT WITH AN
 AREA OF 1,250 S. F. / 30= 42 OCC. FOR THE GALLERY,
 LIBRARY 344 S. F. / 30= 12 OCC. AND STORAGE 236 S. F. /
 300= 1 OCC. FOR A TOTAL OF 50 OCCUPANTS. THIS WOULD
 REQUIRE 2 EGRESS DOORS, BOTH THE GALLERY AND LIBRARY
 DOORS CAN SERVE THIS PURPOSE BUT WILL NEED TO SHOW EXIT
 LIGHTS OVER THESE DOORS IN COMPLIANCE WITH THE 2017
 FBC-B SECTION 1108.2. PLEASE ALSO DEVELOP A LIFE SAFETY
 PLAN SHOWING MEANS OF EGRESS, COMMON PATH OF TRAVEL,
 AND OCCUPANT LOADS ON THE LIFE SAFETY PLAN.
  
 7) IN THE 2017 EXIST. FBC SHOW COMPLIANCE WITH SECTIONS
 1012.2 FIRE PROTECTION SYSTEMS. FIRE PROTECTION SYSTEMS
 SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS 1012.2.1
 AND 1012.2.2.
  
  
 7A) EXIST. BUILD. CODE 1012.2.1 FIRE SPRINKLER SYSTEM.
 WHERE A CHANGE IN OCCUPANCY CLASSIFICATION OCCURS OR
 WHERE THERE IS A CHANGE OF OCCUPANCY WITHIN A SPACE
 WHERE THERE IS A DIFFERENT FIRE PROTECTION SYSTEM
 THRESHOLD REQUIREMENT IN CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING THAT REQUIRES AN AUTOMATIC FIRE
 SPRINKLER SYSTEM TO BE PROVIDED BASED ON THE NEW
 OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING, SUCH SYSTEM SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS.
  
  
 7B) EXIST. BUILD. CODE 1012.2.2 FIRE ALARM AND
 DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS OR WHERE THERE IS A CHANGE OF
 OCCUPANCY WITHIN A SPACE WHERE THERE IS A DIFFERENT
 FIRE PROTECTION SYSTEM THRESHOLD REQUIREMENT IN CHAPTER
 9 OF THE FLORIDA BUILDING CODE, BUILDING THAT REQUIRES
 A FIRE ALARM AND DETECTION SYSTEM TO BE PROVIDED BASED
 ON THE NEW OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF
 THE FLORIDA BUILDING CODE, BUILDING, SUCH SYSTEM SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS. EXISTING ALARM NOTIFICATION
 APPLIANCES SHALL BE AUTOMATICALLY ACTIVATED THROUGHOUT
 THE BUILDING. WHERE THE BUILDING IS NOT EQUIPPED WITH A
 FIRE ALARM SYSTEM, ALARM NOTIFICATION APPLIANCES SHALL
 BE PROVIDED THROUGHOUT THE AREA WHERE THE CHANGE OF
 OCCUPANCY OCCURS IN ACCORDANCE WITH SECTION 907 OF THE
 FLORIDA BUILDING CODE, BUILDING AS REQUIRED FOR NEW
 CONSTRUCTION.
  
 8) PLEASE SHOW HOW COMPLIANCE WITH THE 2017 EXIST.
 BUILD. CODE SECTION 1012.1.4 WILL BE ACHIEVED. 1012.1.4
 ACCESSIBILITY. ALL BUILDINGS UNDERGOING A CHANGE OF
 OCCUPANCY CLASSIFICATION SHALL COMPLY WITH SECTION
 1012.8. 1012.8 ACCESSIBILITY. EXISTING BUILDINGS THAT
 UNDERGO A CHANGE OF GROUP OR OCCUPANCY CLASSIFICATION
 SHALL COMPLY WITH THE PROVISIONS OF THE FLORIDA
 BUILDING CODE, ACCESSIBILITY.
 NOTICE: 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE.
 ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND
 SPACES SHALL COMPLY WITH THE REQUIREMENTS OF THE
 FLORIDA BUILDING CODE, BUILDING.
  
 8A) WHEN STRUCTURES ARE ALTERED, AND OR GO THROUGH A
 CHANGE OF OCCUPANCY THE BUILDING IS LOOKED AT FOR
 ACCESSIBILITY ISSUES. NEW CONSTRUCTION ELEMENTS HAVE TO
 COMPLY WITH ACCESSIBILITY. EXISTING ELEMENTS THAT DO
 NOT COMPLY ONLY 20 % OF THE CONTRACT VALUE (THAT MAY
 INCREASE DEALING WITH CODE ISSUES THAT HAVE TO BE
 BROUGHT UP TO CODE). THE PLANS WERE SUBMITTED WITH A
 CONSTRUCTION VALUE OF $75,000 DOLLARS OF VALUE, TO
 BRING ACCESSIBLE ELEMENTS UP TO CODE UP TO AN
 ADDITIONAL $15,000.00 MAY HAVE TO BE SPENT AND IN THIS
 ORDER.
 2017 FBC- ACCESS. CODE. 202.4.2 ACCESSIBLE FEATURES IN
 THE EVENT OF DISPROPORTIONALITY. WHEN THE COST OF
 ALTERATIONS NECESSARY TO MAKE THE PATH OF TRAVEL TO THE
 ALTERED AREA FULLY ACCESSIBLE IS DISPROPORTIONATE TO
 THE COST OF THE OVERALL ALTERATION, THE PATH OF TRAVEL
 SHALL BE MADE ACCESSIBLE TO THE EXTENT THAT IT CAN BE
 MADE ACCESSIBLE WITHOUT INCURRING DISPROPORTIONATE
 COSTS. IN CHOOSING WHICH ACCESSIBLE ELEMENTS TO
 PROVIDE, PRIORITY SHOULD BE GIVEN TO THOSE ELEMENTS
 THAT WILL PROVIDE THE GREATEST ACCESS, IN THE FOLLOWING
 ORDER: (I) AN ACCESSIBLE ENTRANCE; (II) AN ACCESSIBLE
 ROUTE TO THE ALTERED AREA; (III) AT LEAST ONE
 ACCESSIBLE RESTROOM FOR EACH SEX OR A SINGLE UNISEX
 RESTROOM; (IV) ACCESSIBLE TELEPHONES; (V) ACCESSIBLE
 DRINKING FOUNTAINS; AND (VI) WHEN POSSIBLE, ADDITIONAL
 ACCESSIBLE ELEMENTS SUCH AS PARKING, STORAGE, AND
 ALARMS.
  
 EITHER THE DESIGNER OF RECORD OR CONTRACTOR ON THEIR
 LETTERHEAD CAN SUBMIT A BREAK DOWN WHERE THESE FUNDS
 ARE TO BE SPENT IN THE CASE ALL OF THE ACCESSIBLE
 ELEMENTS CANNOT BE FIXED WITH THE STATED DOLLAR AMOUNT
 GIVEN. THE REMAINDER OF THE ACCESSIBLE ELEMENTS THAT
 WERE NOT CORRECTED CAN BE LEFT AS IS, THE
 DISPROPORTIONALITY HAS BEEN MET.
  
 8B) THE PLANS WILL NEED TO SHOW THAT THERE IS AN
 ACCESSIBLE ENTRANCE AND BECAUSE THE REQUIREMENT FOR 2
 EXITS BOTH DOORS FROM THE GALLERY/ LIBRARY WILL NEED TO
 SHOW THEY ARE AT GRADE AND ACCESSIBLE.
  
 2 ACCESSIBLE MEANS OF EGRESS REQUIRED. 2017
 FBC-ACCESSIBILITY CODE SECTION 207.1 MEANS OF EGRESS
 SHALL COMPLY WITH SECTION 1003.2.13 OF THE
 INTERNATIONAL BUILDING CODE (2000 EDITION AND 2001
 SUPPLEMENT) OR SECTION 1007 OF THE INTERNATIONAL
 BUILDING CODE (2003 EDITION).
  
 2003 IBC-B 1007.1 WHERE MORE THAN ONE MEANS OF EGRESS
 IS REQUIRED BY SECTIONS 1014.1 OR 1018.1 FROM ANY
 ACCESSIBLE SPACE, EACH ACCESSIBLE PORTION OF THE SPACE
 SHALL BE SERVED BY NOT LESS THAN TWO MEANS OF EGRESS.
  
 8C) PLEASE NOTE THE SHEET A1.01 DOES NOT SHOW
 RESTROOMS, DRINKING FOUNTAINS NOR A SERVICE SINK IN THE
 GALLERY / LIBRARY OCCUPANCY. THE FLOOR PLAN A1.01 DOES
 NOT SHOW ANY RESTROOMS WITHIN THE GALLERY / LIBRARY
 OCCUPANCY. PLEASE PROVIDE THE OCCUPANT LOAD AND
 COMPLIANCE WITH THE 2017 FBC-EXIST. BUILD. 1010.1
 REVIEW 1010.6 AND IN THE 2017 FBC-B SECTIONS 2902.1.1,
 2902.2 AND TABLE 2902.1 TO SHOW ACCESSIBLE DRINKING
 FOUNTAINS & RESTROOMS.
  
 8D) THE FLOORPLAN FOR THE RESIDENTIAL UNIT SHOWS A
 RESTROOM, WATERCLOSET AND LAV ONLY PLEASE SHOW WHAT
 SIZE THE POCKET DOOR IS TO THE RESTROOM. 2017
 ACCESSIBILITY CODE 233.3.6 IF ONLY A TOILET ROOM IS
 PROVIDED AT GRADE LEVEL, SUCH TOILET ROOM SHALL HAVE A
 CLEAR OPENING OF 29 INCHES.
  
 8E) THE FLOOR PLAN A1.1 DOES NOT SHOW A DRINKING
 FOUNTAIN. PLEASE PROVIDE COMPLIANCE WITH 2017 FBC-
 ACCESS. CODE SECTION 211.2 MINIMUM NUMBER.
 NO FEWER THAN TWO DRINKING FOUNTAINS SHALL BE PROVIDED.
 ONE DRINKING FOUNTAIN SHALL COMPLY WITH 602.1 THROUGH
 602.6 AND ONE DRINKING FOUNTAIN SHALL COMPLY WITH
 602.7.
 EXCEPTION: WHERE A SINGLE DRINKING FOUNTAIN COMPLIES
 WITH 602.1 THROUGH 602.6 AND 602.7, IT SHALL BE
 PERMITTED TO BE SUBSTITUTED FOR TWO SEPARATE DRINKING
 FOUNTAINS.
  
 9) THE FLOOR PLAN A.1.1. SHOWS IN THE R-3 OCCUPANCY A 2
 STORY UNIT WITH ENCLOSED STAIRWAY ON THE 1ST FLOOR
 LEADING DIRECTLY TO THE EXTERIOR. WHAT THE PLAN DOES
 NOT INDICATE IF THE STAIRWAY IS 1 HOUR FIRE RATED
 WALLS?
 PLEASE PROVIDE OF WHAT MATERIALS THE STAIRWELL WALLS
 ARE MADE OF? 2017 EXIST. BUILD. CODE:
 1012.4.1 MEANS OF EGRESS FOR CHANGE TO HIGHER HAZARD
 CATEGORY.
  
 WHEN A CHANGE OF OCCUPANCY CLASSIFICATION IS MADE TO A
 HIGHER HAZARD CATEGORY (LOWER NUMBER) AS SHOWN IN TABLE
 1012.4, THE MEANS OF EGRESS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 10 OF THE FLORIDA BUILDING
 CODE, BUILDING.
 EXCEPTION 4 DEALS WITH RATED CORRIDOR WALLS BUT THE
 SAME CAN BE USED FOR STAIRWELL WALLS. THE OTHER ISSUE
 IS UNDER THE STAIRWELL THE PLANS SHOW A RESTROOM AND
 WASHER/ DRYER ROOM. WHAT ARE THESE WALLS AND CEILING
 MADE OF?
 EXCEPTIONS:
 4. EXISTING CORRIDOR WALLS CONSTRUCTED ON BOTH SIDES OF
 WOOD LATH AND PLASTER IN GOOD CONDITION OR 1/2-
 INCH-THICK (12.7 MM) GYPSUM WALLBOARD SHALL BE
 PERMITTED. SUCH WALLS SHALL EITHER TERMINATE AT THE
 UNDERSIDE OF A CEILING OF EQUIVALENT CONSTRUCTION OR
 EXTEND TO THE UNDERSIDE OF THE FLOOR OR ROOF NEXT
 ABOVE.
  
 10) SHEET A.1.1 SHOWS A NEW STOREFRONT DOORS AND GARAGE
 DOOR PLEASE PROVIDE COMPLIANCE WITH:
 2017 FBC-B 1609.1.2 PROTECTION OF OPENINGS,
 1609.6.4.4.1 COMPONENTS & CLADDING. FLORIDA DEPARTMENT
 OF COMMUNITY AFFAIRS, ADMINISTRATIVE CODE 61G20-3.005,
 RULE 9N-3 NOV. 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS
 OR CONSTRUCTION SYSTEMS THAT WILL REQUIRE PRODUCT
 APPROVALS:
 (31)(A) EXTERIOR DOORS ,OVERHEAD GARAGE DOOR
 (B) WINDOWS AND MULLIONS (POSSIBLE SIDELIGHTS)
  
 11) IDENTIFY GLAZING/ MULLIONS. PLEASE IDENTIFY ON THE
 PRODUCT APPROVAL BEFORE SUBMITTING TO DESIGNER OF
 RECORD AND BEFORE SUBMISSION TO THE BUILDING
 DEPARTMENT. FOR ALL PRODUCTS WITH GLAZING, PLEASE
 IDENTIFY THE OPENING WIDTH & HEIGHT, TYPE OF GLAZING,
 MULLION SIZE, LENGTH IF UNREINFORCED OR REINFORCED
 INFORMATION IF REQUIRED, ATTACHMENTS AND ASSOCIATE
 PRESSURES FOR EACH OPENING SIZE. 2017 FBC-B 1405.13.1
 INSTALLATION. WINDOWS AND DOORS SHALL BE INSTALLED IN
 ACCORDANCE WITH APPROVED MANUFACTURER?S INSTRUCTIONS.
 FASTENER SIZE AND SPACING SHALL BE PROVIDED IN SUCH
 INSTRUCTIONS AND SHALL BE CALCULATED BASED ON MAXIMUM
 LOADS AND SPACING USED IN THE TESTS.
  
 12) W. P. B. 107.3.4.1 PRODUCT APPROVALS. THOSE
 PRODUCTS WHICH ARE REGULATED BY THE DCA RULE 9N-03
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. FL 61G1-23.015 (2) THE
 ARCHITECT IS RESPONSIBLE FOR SUPERVISING AND REVIEWING
 ALL PROJECT DATA, REPORTS, SHOP DRAWINGS ETC..
  
 13) 107.3.4.2 DEFERRED SUBMITTALS. FOR THE PURPOSES OF
 THIS SECTION, DEFERRED SUBMITTALS ARE DEFINED AS THOSE
 PORTIONS OF THE DESIGN THAT ARE NOT SUBMITTED AT THE
 TIME OF THE APPLICATION AND THAT ARE TO BE SUBMITTED TO
 THE BUILDING OFFICIAL WITHIN A SPECIFIED PERIOD.
 DEFERRAL OF ANY SUBMITTAL ITEMS SHALL HAVE THE PRIOR
 APPROVAL OF THE BUILDING OFFICIAL. THE REGISTERED
 DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE SHALL LIST
 THE DEFERRED SUBMITTALS ON THE CONSTRUCTION DOCUMENTS
 FOR REVIEW BY THE BUILDING OFFICIAL.
  
 DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE
 SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN
 RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD
 THEM TO THE BUILDING OFFICIAL WITH A NOTATION
 INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE
 BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO
 THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL
 ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED
 SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING
 OFFICIAL.
  
 14) SHEET A1.1 WITH NEW EXTERIOR DOORS WE WILL NEED TO
 HAVE THE WIND DESIGN CRITERIA.
 2017 FBC-B 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL FORCE-RESISTING SYSTEM OF THE
 STRUCTURE:
  
 14.1. ULTIMATE DESIGN WIND SPEED, VULT, (3-SECOND
 GUST), MILES PER HOUR AND NOMINAL DESIGN WIND SPEED,
 VASD, AS DETERMINED IN ACCORDANCE WITH SECTION
 1609.3.1.
  
 14.2. RISK CATEGORY.
  
 14.3. WIND EXPOSURE. APPLICABLE WIND DIRECTION IF MORE
 THAN ONE WIND EXPOSURE IS UTILIZED. TABLE 1609.7.2.
 HEIGHT AND EXPOSURE.
  
 14.4. APPLICABLE INTERNAL PRESSURE COEFFICIENT.
  
 14.5. DESIGN WIND PRESSURES TO BE USED FOR EXTERIOR
 COMPONENTS AND CLADDING MATERIALS NOT SPECIFICALLY
 DESIGNED BY THE REGISTERED DESIGN PROFESSIONAL
 RESPONSIBLE FOR THE DESIGN OF THE STRUCTURE, PSF.
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 15) CITY AND COUNTY RECORDS INDICATE THIS STRUCTURE WAS
 BUILT IN 1964 WHEN ASBESTOS WAS USED IN CONSTRUCTION.
 IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO
 ADVISE YOU OF THE OWNERS OR OPERATORS? RESPONSIBILITY
 TO COMPLY WITH THE STATE & FEDERAL ASBESTOS
 REGULATIONS, INCLUDING SECTION 376.60 F. S. AND CFR 61-
 NESHAP REQUIREMENTS. REQUIREMENTS INCLUDE- ASBESTOS
 SURVEYS AND SUBMISSION OF WRITTEN NOTIFICATION TO THE
 DEPARTMENT OF ENVIRONMENTAL PROTECTION PRIOR TO: *
 DEMOLITION OF ALL REGULATED STRUCTURES;
 * MOST RENOVATION ACTIVITIES IN REGULATED STRUCTURES
 WHERE ASBESTOS IS DISTURBED OR REMOVED.
 NON-COMPLIANCE MAY RESULT IN SEVERE MONETARY PENALTY.
  
 FOR FURTHER INFORMATION IN PALM BEACH COUNTY, CONTACT
 THE DIVISION OF ENVIRONMENTAL HEALTH AND ENGINEERING
 HRS/ PALM BEACH COUNTY PUBLIC HEALTH UNIT
 (DIVISION OF ENGINEERING SCIENCE & ENGINEERING AIR
 POLLUTION CONTROL SECTION)
  
 901 EVERNIA STREET
 WEST PALM BEACH, FL 33401
 (561) 355-3070
  
 16) IMPACT FEES- PAPER SUBMITTALS. PLANS REQUIRE REVIEW
 BY THE PBC IMPACT FEE OFFICE. CALL (561) 233-5025. UPON
 APPROVAL, YOU MAY CHECK OUT ONE PLAN SET AND TAKE TO
 THAT OFFICE FOR REVIEW. PLEASE RETURNED STAMPED AND
 WITH A COPY OF THE RECEIPT AS APPLICABLE. PLEASE
 PROVIDE THE MUNICIPAL IMPACT FEE QUESTIONNAIRE FORM TO
 THE PBC IMPACT FEE OFFICE. THE FORM CAN BE FOUND AT:
 HTTP://DISCOVER.PBCGOV.ORG/PZB/ADMINISTRATION/PDF/IMPAC
 TFEES/FORMS/QUESTIONNAIRE.PDF
  
 17) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE
 THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED
 DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE
 MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS
 AND INFORMATION LACKING UNDER THE PRIOR REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT
 401 CLEMATIS ST. WEST PALM BEACH. FL 33402
 TEL: 561-805-6717 / FAX: 561-805-6676
 E-MAIL: [email protected]
  