Date |
Text |
2019-08-27 11:03:06 | JONATHAN BROOKS JR. |
| BUILDING PLANS EXAMINER |
| WORK HOURS TUESDAY & THURSDAY 7:00 AM TO 3:00 PM |
| (561) 805-6716 ALTERNATE: CONTACT SAMANTHA HILL (561) |
| 805-6724 |
| [email protected] |
| |
| 1ST REVIEW: FBC 2017 6TH EDITION |
| FBC = FLORIDA BUILDING CODE, 6TH EDITION (2017) |
| FBC B = FBC BUILDING |
| FBC R = FBC RESIDENTIAL |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| WPB A = CITY OF WEST PALM BEACH AMENMENTS TO THE FBC |
| RESULTS: DENIED |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| YOU MAY RESUBMIT UP TO TWO PAGES, ALONG WITH A |
| COMPLETED RESUBMITTAL FORM, VIA EMAIL TO |
| [email protected]. THE EMAIL SHOULD INCLUDE THE PERMIT |
| NUMBER AND "RESUBMITTAL" IN THE SUBJECT LINE. THE |
| RESUBMITTAL FORM CAN BE FOUND AT THIS WEBSITE: |
| HTTP://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/B |
| UILDING-PERMIT-FORMS |
| |
| 1.FBC B 107.2.1. ON THE SCHEDULE FOR INSTALLATION OF |
| PROTECTIVE DEVICES OR ASSEMBLIES: COLUMN HEADING |
| ?SHUTTER MOUNTING CONNECTION TYPE PER PRODUCT |
| APPROVAL?; PROVIDE INFORMATION FROM SHEETS 6 & 7 OF |
| FL389-R9 USE ALPHABETICAL LETTER THAT CORRESPONDS WITH |
| THE CONNECTION TYPE FOR THE TOP AND BOTTOM CONNECTIONS. |
| HEADING ?SHUTTER SPAN?; PROVIDE INFORMATION FROM SHEET |
| 5 FL389-R9, THE TOP OF THE SHUTTER BLADE TO THE BOTTOM |
| OF THE SHUTTER BLADES LENGTH. ACCORDION SHUTTERS ARE |
| INSTALLED VERTICALLY AS PER PAGE 5 OF FL389-R9; CORRECT |
| COLUMN HEADING ?SHUTTER INSTALLED VERTICAL/HORIZONTAL. |
| |