Plan Review Notes For Permit 19080775
Permit Number 19080775
Review Stop B
Sequence Number 1
Notes
Date Text
2019-09-06 16:06:04BUILDING REVIEW COMMENTS:
  
 W.P.B. PERMIT: 19080775
 REVIEWED: SEPTEMBER 6, 2019
  
 DYLAN BATTLES
 BUILDING PLANS EXAMINER PX4191
 [email protected]
 561-805-6718
  
 FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017)
 FBC[B] = FBC BUILDING
 FBC[EXISTING] = FBC EXISTING BUILDING
 FBC[A] = FBC ACCESSIBILITY
 FBC[E] = FBC ENERGY CONSERVATION
 FBC[R] = FBC RESIDENTIAL
  
 1) 301.2(7)FIGURE FBC[R]PROVIDE WIND DIAGRAM THAT
 MATCHES THE ROOF CONDITION OF THIS HOUSE.
  
 2) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO
 KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT
 PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU
 CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE
 PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING
 STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION
 CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB
 LIC-WORKS/FORMS,-PERMITS-APPLICATIONS
  
 3) [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE
 DRAINAGE PLAN. SURFACE DRAINAGE SHALL BE DIVERTED TO A
 STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF
 COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE
 GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION
 WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES
 WITHIN THE FIRST 10 FEET. EXCEPTION: WHERE LOT LINES,
 WALLS, SLOPES OR OTHER PHYSICAL BARRIERS PROHIBIT 6
 INCHES OF FALL WITHIN 10 FEET (3048 MM), DRAINS OR
 SWALES SHALL BE CONSTRUCTED TO ENSURE DRAINAGE AWAY
 FROM THE STRUCTURE. IMPERVIOUS SURFACES WITHIN 10 FEET
 OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF
 2 PERCENT AWAY FROM THE BUILDING.
 -
  
 4) 403.1.7.3 FBC[R] FOUNDATION ELEVATION. ON GRADED
 SITES, THE TOP OF ANY EXTERIOR FOUNDATION SHALL EXTEND
 ABOVE THE ELEVATION OF THE STREET GUTTER AT POINT OF
 DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE A
 MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT. ALTERNATE
 ELEVATIONS ARE PERMITTED SUBJECT TO THE APPROVAL OF THE
 BUILDING OFFICIAL, PROVIDED IT CAN BE DEMONSTRATED THAT
 REQUIRED DRAINAGE TO THE POINT OF DISCHARGE AND AWAY
 FROM THE STRUCTURE IS PROVIDED AT ALL LOCATIONS ON THE
 SITE.
  
 5) 703.4 FBC[R] PROVIDE TYPE OF WINDOW/DOOR FLASHING TO
 BE USED TO MEET REQUIREMENTS OF R703.4
  
 6) 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES
 REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH
 THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD
 INDEX AND SMOKE DEVELOPED INDEX.
  
 7) INDICATE THE ROOF TILE ATTACHMENT METHOD THAT WILL
 BE USED BY MARKING THE APPROPRIATE INFORMATION ON THE
 PRODUCT APPROVAL. FBC 107.2.1 IF AN ADHESIVE WILL BE
 USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC 107.3.4
 IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE PRODUCT
 APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT WILL MEET
 WINDLOADS.
  
 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 SLIDING GLASS DOOR, ARCH WINDOWS AND MULL BETWEEN, OR
 INDICATE THAT YOU WOULD LIKE IT DEFERRED.
  
 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR
 TILE ROOFING ADHESIVE, OR INDICATE THAT YOU WOULD LIKE
 IT DEFERRED.
  
 PROVISOS:
 DEFERRED SUBMITTALS - ROOF TRUSS SHOP DWGS TO INSPECTOR
 PRIOR TO INSTALLATION.
 PROVIDE ROOFING (TILE) ATTACHMENT OR INDICATE THAT IT
 WILL BE DEFERRED UNTIL ROOFING SUB PERMIT IS APPLIED
 FOR.
 SEPARATE PERMITS REQUIRED FOR-
 DRIVEWAY
 FENCING
 CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM
 SAT-SUN
 - PROVISOS WILL BE ADDED TO THE PLANS AT FINAL
 STAMPING.
  
  
 NOTES:
  
 -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW
 EACH COMMENT IS BEING ADDRESSED.
  
 -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW
 OF MATERIALS REQUESTED.
  
 -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS
 OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS)
 SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT
 DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER
 SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID"
 OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS
 APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE
 NEED "VOID", RENDERING THEM NOT USABLE.
  
 PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F
 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME
 [email protected]
  
  
  