2019-09-06 16:06:04 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19080775 |
| REVIEWED: SEPTEMBER 6, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1) 301.2(7)FIGURE FBC[R]PROVIDE WIND DIAGRAM THAT |
| MATCHES THE ROOF CONDITION OF THIS HOUSE. |
| |
| 2) 107.3.5.3 FBC[AMENDED] PROVIDE SEDIMENT CONTROL TO |
| KEEP CONSTRUCTION DEBRIS FROM ENTERING ADJACENT |
| PROPERTIES AND STORM DRAINS DURING CONSTRUCTION. YOU |
| CAN JUST ADD SILT FENCE DETAIL AND HOW DRAINS ARE |
| PROTECTED TO THE DRAINAGE PLAN. SOME ENGINEERING |
| STANDARD DETAILS CAN BE USED FROM WPB WEBSITE-POLLUTION |
| CONTROL. HTTP://WWW.WPB.ORG/DEPARTMENTS/ENGINEERING-PUB |
| LIC-WORKS/FORMS,-PERMITS-APPLICATIONS |
| |
| 3) [FBC 107.5][FBC 110.9][FBC R401.3][PROVIDE SITE |
| DRAINAGE PLAN. SURFACE DRAINAGE SHALL BE DIVERTED TO A |
| STORM SEWER CONVEYANCE OR OTHER APPROVED POINT OF |
| COLLECTION THAT DOES NOT CREATE A HAZARD. LOTS SHALL BE |
| GRADED TO DRAIN SURFACE WATER AWAY FROM FOUNDATION |
| WALLS. THE GRADE SHALL FALL A MINIMUM OF 6 INCHES |
| WITHIN THE FIRST 10 FEET. EXCEPTION: WHERE LOT LINES, |
| WALLS, SLOPES OR OTHER PHYSICAL BARRIERS PROHIBIT 6 |
| INCHES OF FALL WITHIN 10 FEET (3048 MM), DRAINS OR |
| SWALES SHALL BE CONSTRUCTED TO ENSURE DRAINAGE AWAY |
| FROM THE STRUCTURE. IMPERVIOUS SURFACES WITHIN 10 FEET |
| OF THE BUILDING FOUNDATION SHALL BE SLOPED A MINIMUM OF |
| 2 PERCENT AWAY FROM THE BUILDING. |
| - |
| |
| 4) 403.1.7.3 FBC[R] FOUNDATION ELEVATION. ON GRADED |
| SITES, THE TOP OF ANY EXTERIOR FOUNDATION SHALL EXTEND |
| ABOVE THE ELEVATION OF THE STREET GUTTER AT POINT OF |
| DISCHARGE OR THE INLET OF AN APPROVED DRAINAGE DEVICE A |
| MINIMUM OF 12 INCHES (305 MM) PLUS 2 PERCENT. ALTERNATE |
| ELEVATIONS ARE PERMITTED SUBJECT TO THE APPROVAL OF THE |
| BUILDING OFFICIAL, PROVIDED IT CAN BE DEMONSTRATED THAT |
| REQUIRED DRAINAGE TO THE POINT OF DISCHARGE AND AWAY |
| FROM THE STRUCTURE IS PROVIDED AT ALL LOCATIONS ON THE |
| SITE. |
| |
| 5) 703.4 FBC[R] PROVIDE TYPE OF WINDOW/DOOR FLASHING TO |
| BE USED TO MEET REQUIREMENTS OF R703.4 |
| |
| 6) 302.10 FBC[R] PROVIDE CUT SHEET FOR ICYNENE(ICC-ES |
| REPORT OR EQUAL) WITH THE TYPE SELECTED TO ESTABLISH |
| THICKNESS NEEDED TO MEET REQUIRED R-VALUE, FLAME SPREAD |
| INDEX AND SMOKE DEVELOPED INDEX. |
| |
| 7) INDICATE THE ROOF TILE ATTACHMENT METHOD THAT WILL |
| BE USED BY MARKING THE APPROPRIATE INFORMATION ON THE |
| PRODUCT APPROVAL. FBC 107.2.1 IF AN ADHESIVE WILL BE |
| USED, SUBMIT THE PRODUCT APPROVAL FOR IT. FBC 107.3.4 |
| IF A MORTAR OR ADHESIVE SET IS USED SUBMIT THE PRODUCT |
| APPROVAL FOR THE UNDERLAYMENT TO SHOW THAT IT WILL MEET |
| WINDLOADS. |
| |
| 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| SLIDING GLASS DOOR, ARCH WINDOWS AND MULL BETWEEN, OR |
| INDICATE THAT YOU WOULD LIKE IT DEFERRED. |
| |
| 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| TILE ROOFING ADHESIVE, OR INDICATE THAT YOU WOULD LIKE |
| IT DEFERRED. |
| |
| PROVISOS: |
| DEFERRED SUBMITTALS - ROOF TRUSS SHOP DWGS TO INSPECTOR |
| PRIOR TO INSTALLATION. |
| PROVIDE ROOFING (TILE) ATTACHMENT OR INDICATE THAT IT |
| WILL BE DEFERRED UNTIL ROOFING SUB PERMIT IS APPLIED |
| FOR. |
| SEPARATE PERMITS REQUIRED FOR- |
| DRIVEWAY |
| FENCING |
| CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| SAT-SUN |
| - PROVISOS WILL BE ADDED TO THE PLANS AT FINAL |
| STAMPING. |
| |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |