Plan Review Notes For Permit 19080773 |
Permit Number |
19080773 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-10-28 09:12:26 | GAS 2ND REVIEW**DENIED**19080773 | | | | 1) UNABLE TO LOCATE THE GAS APPLIANCES INSTALLATION | | MANUALS. PLEASE PROVIDE. FBC 107.2.1 | | 2) YOUR R405/2017 LIST THE WATER HATER AS 60 GALLON | | TANK TYPE BUT SHT. P 1.01 CALLS OUT 2 NAVIEN TANKLESS | | WATER HEATERS. PLEASE CLARIFY AND IF NOT USING 60 | | GALLON TANK TYPE PLEASE REVISE AND RESUBMIT YOUR | | R405/2017. FBC 107.3.5 | | 3) PLEASE LIST THE GENERATOR AS REQUIRING ALL TRADES | | SEPARATE PERMITS. WPB AMEND 105.1 | | | | TIM HUNT | | PLUMBING PLANS EXAMINER | | CITY OF WEST PALM BEACH ( CGA SOLUTIONS) | | [email protected] | | 561-248-2703 | | |
|