2019-09-25 17:14:53 | 1ST REVIEW: 19080773 |
| 2017 FLORIDA BUILDING CODE 6TH EDITION |
| 2017 FLORIDA BUILDING CODE - PLUMBING, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - ACCESSIBILITY, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - FUEL GAS, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - RESIDENTIAL, SIXTH EDITION |
| 2017 FLORIDA BUILDING CODE - EXISTING BUILDING, SIXTH |
| EDITION |
| 2017 FLORIDA BUILDING CODE - ENERGY CONSERVATION, SIXTH |
| EDITION |
| |
| GAS COMMENTS: |
| |
| 1. IS THE CSST RUNNING UNDER THE LAB A SLEEVE MAY BE |
| REQUIRED PROVIDE DETAIL OR MANUFACTURE SPECIFICATIONS |
| FOR GAS PIPING UNDER SLAB. PER WPB AMEND TO FBC 107.2.1 |
| |
| 2. PLEASE PROVIDE MANUFACTURE SPECIFICATION AND |
| INSTILLATION GUIDE FOR ALL GAS APPLIANCE AND |
| REGULATORS. PER WPB AMEND TO FBC 107.2.1 |
| |
| 3. WHERE A SEDIMENT TRAP IS NOT INCORPORATED AS PART OF |
| THE APPLIANCE, A SEDIMENT TRAP SHALL BE INSTALLED |
| DOWNSTREAM OF THE APPLIANCE SHUTOFF VALVE AS CLOSE TO |
| THE INLET OF THE APPLIANCE AS PRACTICAL. THE SEDIMENT |
| TRAP SHALL BE EITHER A TEE FITTING HAVING A CAPPED |
| NIPPLE OF ANY LENGTH INSTALLED VERTICALLY IN THE |
| BOTTOMMOST OPENING OF THE TEE AS ILLUSTRATED IN FIGURE |
| 408.4 OR OTHER DEVICE APPROVED AS AN EFFECTIVE SEDIMENT |
| TRAP.PER FBC FG 408.4 |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS. |
| |