Plan Review Notes For Permit 19080773 |
Permit Number |
19080773 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-09-21 10:38:53 | ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. | | 1. GARAGE DOOR OPENER GFCI RECEPTACLES NOT READILY | | ACCESSIBLE. NEC 210.8 | | 2. NO DISCONNECTS SHOWN FOR AC C/U?S OUTSIDE. FBC | | 107.2.1 | | 3. ALL BALCONIES REQUIRE MINIMUM 1 GFCI PROTECTED | | RECEPTACLE NEC 210.53E3 | | 4. SMOKE/CO ALARMS REQUIRED PER FBC RE 314&315 | | 5. TWO ATS?S SHOWN ON RISER DIAGRAM BUT ONLY ONE SHOWN | | ON PLAN, PLEASE PROVIDE CORRECTION. FBC 107.2.1 | | | | END OF COMMENTS. | | | | PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED | | MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN | | RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES | | INTO THE ORIGINAL SUBMITTAL AND REMOVE OR VOID THE | | PREVIOUSLY REVIEWED SHEETS. | | CODES IN EFFECT: | | FBC = FLORIDA BUILDING CODE 2017 6TH EDITION | | WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FLORIDA | | BUILDING CODE 2017 6TH ED. | | FBC EB = FLORIDA BUILDING CODE EXISTING BUILDING 2017 | | 6TH EDITION | | FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 | | 6TH EDITION | | FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION | | NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE | | FS = FLORIDA STATUTES | | | | V/R, | | FRANK GIAQUINTO III | | ELECTRICAL INSPECTOR | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | [email protected] | | CELL: 561-657-1653 | | | | |
|