Notes
Date Text
2019-10-01 15:11:41PLUMBING COMMENTS: APPROVED W/PROVISO
  
 1. ARCHITECT SHALL PROVIDE AS A REVISION A DETAIL OF
 THE FLAT ROOF CLEARLY SHOWING THE PERIMETER DOES NOT
 EXTEND ABOVE THE ROOF AS HE STATED WAS STATED IN
 RESPONSE TO PLUMBING COMMENTS DATED 9/10/19. PLAN SHEET
 A-300 DOES NOT CLEARLY SHOW THIS TO BE THE CASE. PER
 FBC PL 1108.1, SECONDARY DRAINS ARE REQUIRED WHERE ROOF
 PERIMETER CONSTRUCTION ALLOWS WATER TO BE ENTRAPPED IF
 THE PRIMARY DRAIN(S) ALLOW BUILD UP IN ANY MANNER. THE
 DOCUMENT(S) SHALL BE SUBMITTED, APPROVED AND ON SITE
 PRIOR TO FINAL INSPECTION. PROCEED AT YOUR OWN RISK.
 2. ALL WORK PER STATE AND CITY CODES SUBJECT TO FIELD
 INSPECTOR'S APPROVAL