Plan Review Notes
Plan Review Notes For Permit 19080742
Permit Number 19080742
Review Stop P
Sequence Number 1
Notes
Date Text
2019-09-10 15:59:36CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 PLUMBING COMMEMTS: DENIED
 1. FBC RES P2601.1 SCOPE.
 THE PROVISIONS OF THIS CHAPTER SHALL GOVERN THE
 INSTALLATION OF PLUMBING NOT SPECIFICALLY COVERED IN
 OTHER CHAPTERS APPLICABLE TO PLUMBING SYSTEMS. THE
 INSTALLATION OF PLUMBING, APPLIANCES, EQUIPMENT AND
 SYSTEMS NOT ADDRESSED BY THIS CODE SHALL COMPLY WITH
 THE APPLICABLE PROVISIONS OF THE FLORIDA BUILDING CODE,
 PLUMBING.
 A. FBC PL 1108.1 SECONDARY (EMERGENCY OVERFLOW) DRAINS
 OR SCUPPERS.
 WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY
 OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED
 WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE
 ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF
 THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON. WHERE
 PRIMARY AND SECONDARY ROOF DRAINS ARE MANUFACTURED AS A
 SINGLE ASSEMBLY, THE INLET AND OUTLET FOR EACH DRAIN
 SHALL BE INDEPENDENT.
 B. FBC PL 802.3 WASTE RECEPTOR FOR ICEMAKER DISCHARGE
 SHALL BE READILY ACCESSIBLE
 2. WPB FBC 107.2.1 VALID DIGITAL SIGNATURE OF DESIGNER
 IS REQUIRED.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
 AS THE PLANS ARE NOT SIGNED AND SEALED BY A
 PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN
 SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE
 DESIGNER PER WPB FBC 107.2.1.
  
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080742 125 ALHAMBRA PL
  
  
  
  
  
  
  
  
  
  