Date |
Text |
2019-09-10 15:59:36 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| PLUMBING COMMEMTS: DENIED |
| 1. FBC RES P2601.1 SCOPE. |
| THE PROVISIONS OF THIS CHAPTER SHALL GOVERN THE |
| INSTALLATION OF PLUMBING NOT SPECIFICALLY COVERED IN |
| OTHER CHAPTERS APPLICABLE TO PLUMBING SYSTEMS. THE |
| INSTALLATION OF PLUMBING, APPLIANCES, EQUIPMENT AND |
| SYSTEMS NOT ADDRESSED BY THIS CODE SHALL COMPLY WITH |
| THE APPLICABLE PROVISIONS OF THE FLORIDA BUILDING CODE, |
| PLUMBING. |
| A. FBC PL 1108.1 SECONDARY (EMERGENCY OVERFLOW) DRAINS |
| OR SCUPPERS. |
| WHERE ROOF DRAINS ARE REQUIRED, SECONDARY (EMERGENCY |
| OVERFLOW) ROOF DRAINS OR SCUPPERS SHALL BE PROVIDED |
| WHERE THE ROOF PERIMETER CONSTRUCTION EXTENDS ABOVE THE |
| ROOF IN SUCH A MANNER THAT WATER WILL BE ENTRAPPED IF |
| THE PRIMARY DRAINS ALLOW BUILDUP FOR ANY REASON. WHERE |
| PRIMARY AND SECONDARY ROOF DRAINS ARE MANUFACTURED AS A |
| SINGLE ASSEMBLY, THE INLET AND OUTLET FOR EACH DRAIN |
| SHALL BE INDEPENDENT. |
| B. FBC PL 802.3 WASTE RECEPTOR FOR ICEMAKER DISCHARGE |
| SHALL BE READILY ACCESSIBLE |
| 2. WPB FBC 107.2.1 VALID DIGITAL SIGNATURE OF DESIGNER |
| IS REQUIRED. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| AS THE PLANS ARE NOT SIGNED AND SEALED BY A |
| PROFESSIONAL ENGINEER OR ARCHITECT, THE PLUMBING PLAN |
| SHALL BEAR THE PRINTED NAME AND SIGNATURE OF THE |
| DESIGNER PER WPB FBC 107.2.1. |
| |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19080742 125 ALHAMBRA PL |
| |
| |
| |
| |
| |
| |
| |
| |
| |
| |