Date |
Text |
2019-09-16 13:14:52 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL |
| MANUAL REVISED 2017 |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION |
| FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH |
| EDITION |
| FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION |
| FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION |
| NFPA 54 = NATIONAL FUEL GAS CODE |
| NFPA 58 = LIQUIFIED PETROLEUM GAS CODE |
| NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE |
| PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017 |
| NFPA 99 = HEALTH CARE FACILITIES CODE |
| NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES |
| FAC= FLORIDA ADMINISTRATIVE CODE |
| FS = FLORIDA STATUTES |
| |
| |
| 1ST REVIEW |
| GAS COMMENTS: DENIED |
| |
| 1. PLEASE NOTE THAT REQUESTS HAVE BEEN MADE FOR CHANGES |
| TO ARCHITECTURAL DRAWINGS AS WELL AS MEP. THESE |
| REQUESTS MUST BE SATISFIED PRIOR TO GAS PERMIT |
| APPROVAL. |
| 2. PER WPB FBC 107.2.1, PROVIDE ON ARCH PLAN SHEET |
| A001, THE LOCATIONS OF THE GAS METER, THE GENERATOR AND |
| THE POOL HEATER. |
| 3. PER WPB FBC 107.2.1, PROVIDE ON ARCH PLAN SHEET A100 |
| AND ON PLAN SHEET P2.1 AN ACCESS PANEL (INCLUDE |
| DIMENSIONS OF PANEL) TO ACCOMMODATE THE ABOVE CEILING |
| REGULATOR SERVING THE FIREPLACE IN ACCORDANCE WITH FBC |
| FG 410.1. |
| 4. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR SLEEVED |
| AND VENTED PE PIPE INSTALLED BELOW A HARD SURFACE. |
| ADDITIONALLY, WHEN LANDSCAPE/HARDSCAPE DRAWINGS ARE |
| SUBMITTED, PER WPB FBC 107.2.1, LOCATIONS OF SLEEVED |
| AND VENTED PIPE SECTIONS SHALL BE INDICATED. |
| 5. RE: PLAN SHEET P0.3; GAS RISER ISOMETRIC. FIREPLACE |
| (40,000 BTUH) IS SHOWN AT THE LOCATION THAT INDICATES A |
| POOL HEATER (400,000 BTUH) ON PLAN SHEET P2.1. PER WPB |
| FBC 107.2.1, PLEASE CLARIFY. |
| 6. RE: PLAN SHEET P0.3; GAS RISER ISOMETRIC. PER WPB |
| FBC 107.2.1, CLEARLY SHOW ON THE ISOMETRIC DRAWING THE |
| LENGTH OF ALL CUT SECTIONS OF PIPE IN ACCORDANCE WITH |
| FBC FG SECS. 402.4.1, 402.4.2. OR FBC RES SEC. |
| G2413.4.1, G2413.4.2. |
| 7. PER WPB FBC 107.2.1, PLEASE NOTE IN THE CHART ON |
| P0.3 INDICATING SIZING TABLES AND TOTAL GAS CONSUMPTION |
| THE DISTANCE FROM THE POINT OF DELIVERY, (GAS METER / |
| REGULATOR) TO THE MOST REMOTE OUTLET IN THE BUILDING |
| AND / OR SYSTEM FOR EACH PRESSURE SYSTEM (2 PSI/0.5 |
| PSI) IN ACCORDANCE WITH FBC FG SEC.402.4.1, 402.4.2, OR |
| FBC RES SEC. G 2413.4.1, G2413.4.2. |
| 8. PER WPB FBC 107.2.1, PLEASE NOTE IN THE CHART ON |
| P0.3 INDICATING SIZING TABLES AND TOTAL GAS CONSUMPTION |
| THE TYPE OF GAS (LP OR NATURAL). IT IS ASSUMED TO BE NG |
| DUE TO NOTE ON GAS ISOMETRIC PERTAINING TO NATURAL GAS |
| CONNECTION BUT NEEDS TO BE STATED. |
| 9. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S |
| SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS |
| EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54, |
| NFPA 58, AND FBC FG SEC. 402.2, AND 301.3 OR 2017 FBC |
| RES SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED AND |
| LABELED. |
| 10. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S |
| SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS |
| INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE |
| APPROVED FOR OUTDOOR INSTALLATION IN ACCORDANCE WITH |
| FBC FG SEC.410.1, FBC RES SEC. G2421.1. RE: FBC FG |
| 410.3; INDICATE ON SUBMITTALS FOR INDOORS THE TYPE OF |
| VENT ELIMINATOR IS TO BE USED OR PROVIDE ON THE PLANS, |
| VENT PIPING (MATERIAL TYPE, SIZE AND ROUTING) TO THE |
| EXTERIOR WITH DETAIL OF EXTERIOR TERMINATION IN |
| ACCORDANCE WITH FBC FG IN ACCORDANCE WITH FBC FG SECS. |
| 502 THRU 505 OR FBC RES SEC.G2426 THROUGH G2439. |
| 11. PER WPB FBC 107.2.1, IN ADDITION TO THE COMBUSTION |
| AIR CALCULATIONS PROVIDED FOR THE DRYER ON PLAN SHEET |
| M0-2, SUBMIT COMBUSTION AIR CALCULATIONS FOR THE |
| ADDITIONAL INDOOR GAS APPLIANCES. WHERE COMBUSTION AIR |
| IS PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION |
| SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED |
| COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED |
| VENTILATION AIR IN ACCORDANCE WITH FBC FG SEC.304.9.3 |
| OR FBC RES G2407.9.3. |
| |
| |
| END OF COMMENTS. |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID |
| THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED |
| AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS. |
| |
| |
| JERALD SMITH |
| PLUMBING PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| EMAIL [email protected] |
| PHONE 561-805-6715 |
| |
| 19080742 125 ALHAMBRA PL |
| |
| |
| |