Plan Review Notes
Plan Review Notes For Permit 19080742
Permit Number 19080742
Review Stop G
Sequence Number 1
Notes
Date Text
2019-09-16 13:14:52CODES IN EFFECT:
 FBC = FLORIDA BUILDING CODE 2017 6TH EDITION
 WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017
 6TH ED, CHAPTER 1.
 WPB CCCM=WEST PALM BEACH CROSS-CONNECTION CONTROL
 MANUAL REVISED 2017
 FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017
 6TH EDITION
 FBC RES = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION
 FBC ACC = FLORIDA ACCESSIBILITY CODE 2017 6TH EDITION
 FBC EX = FLORIDA EXISTING BUILDING CODE 2017 6TH
 EDITION
 FBC PL = FLORIDA PLUMBING CODE 2017 6TH EDITION
 FBC FG = FLORIDA FUEL GAS CODE 2017 6TH EDITION
 NFPA 54 = NATIONAL FUEL GAS CODE
 NFPA 58 = LIQUIFIED PETROLEUM GAS CODE
 NFPA 96 = STANDARD FOR VENTILATION CONTROLAND FIRE
 PROTECTION OF COMMERCIAL COOKING OPERATIONS 2017
 NFPA 99 = HEALTH CARE FACILITIES CODE
 NFPA 99B = STANDARD FOR HYPERBARIC FACILITIES
 FAC= FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
  
  
 1ST REVIEW
 GAS COMMENTS: DENIED
  
 1. PLEASE NOTE THAT REQUESTS HAVE BEEN MADE FOR CHANGES
 TO ARCHITECTURAL DRAWINGS AS WELL AS MEP. THESE
 REQUESTS MUST BE SATISFIED PRIOR TO GAS PERMIT
 APPROVAL.
 2. PER WPB FBC 107.2.1, PROVIDE ON ARCH PLAN SHEET
 A001, THE LOCATIONS OF THE GAS METER, THE GENERATOR AND
 THE POOL HEATER.
 3. PER WPB FBC 107.2.1, PROVIDE ON ARCH PLAN SHEET A100
 AND ON PLAN SHEET P2.1 AN ACCESS PANEL (INCLUDE
 DIMENSIONS OF PANEL) TO ACCOMMODATE THE ABOVE CEILING
 REGULATOR SERVING THE FIREPLACE IN ACCORDANCE WITH FBC
 FG 410.1.
 4. PER WPB FBC 107.2.1, PROVIDE A DETAIL FOR SLEEVED
 AND VENTED PE PIPE INSTALLED BELOW A HARD SURFACE.
 ADDITIONALLY, WHEN LANDSCAPE/HARDSCAPE DRAWINGS ARE
 SUBMITTED, PER WPB FBC 107.2.1, LOCATIONS OF SLEEVED
 AND VENTED PIPE SECTIONS SHALL BE INDICATED.
 5. RE: PLAN SHEET P0.3; GAS RISER ISOMETRIC. FIREPLACE
 (40,000 BTUH) IS SHOWN AT THE LOCATION THAT INDICATES A
 POOL HEATER (400,000 BTUH) ON PLAN SHEET P2.1. PER WPB
 FBC 107.2.1, PLEASE CLARIFY.
 6. RE: PLAN SHEET P0.3; GAS RISER ISOMETRIC. PER WPB
 FBC 107.2.1, CLEARLY SHOW ON THE ISOMETRIC DRAWING THE
 LENGTH OF ALL CUT SECTIONS OF PIPE IN ACCORDANCE WITH
 FBC FG SECS. 402.4.1, 402.4.2. OR FBC RES SEC.
 G2413.4.1, G2413.4.2.
 7. PER WPB FBC 107.2.1, PLEASE NOTE IN THE CHART ON
 P0.3 INDICATING SIZING TABLES AND TOTAL GAS CONSUMPTION
 THE DISTANCE FROM THE POINT OF DELIVERY, (GAS METER /
 REGULATOR) TO THE MOST REMOTE OUTLET IN THE BUILDING
 AND / OR SYSTEM FOR EACH PRESSURE SYSTEM (2 PSI/0.5
 PSI) IN ACCORDANCE WITH FBC FG SEC.402.4.1, 402.4.2, OR
 FBC RES SEC. G 2413.4.1, G2413.4.2.
 8. PER WPB FBC 107.2.1, PLEASE NOTE IN THE CHART ON
 P0.3 INDICATING SIZING TABLES AND TOTAL GAS CONSUMPTION
 THE TYPE OF GAS (LP OR NATURAL). IT IS ASSUMED TO BE NG
 DUE TO NOTE ON GAS ISOMETRIC PERTAINING TO NATURAL GAS
 CONNECTION BUT NEEDS TO BE STATED.
 9. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC FG SEC. 402.2, AND 301.3 OR 2017 FBC
 RES SEC. G2404.3. GAS APPLIANCES SHALL BE LISTED AND
 LABELED.
 10. PER WPB FBC 107.2.1, SUBMIT MANUFACTURER?S
 SPECIFICATIONS FOR THE PRESSURE REGULATORS. REGULATORS
 INSTALLED ON THE EXTERIOR OF THE BUILDING SHALL BE
 APPROVED FOR OUTDOOR INSTALLATION IN ACCORDANCE WITH
 FBC FG SEC.410.1, FBC RES SEC. G2421.1. RE: FBC FG
 410.3; INDICATE ON SUBMITTALS FOR INDOORS THE TYPE OF
 VENT ELIMINATOR IS TO BE USED OR PROVIDE ON THE PLANS,
 VENT PIPING (MATERIAL TYPE, SIZE AND ROUTING) TO THE
 EXTERIOR WITH DETAIL OF EXTERIOR TERMINATION IN
 ACCORDANCE WITH FBC FG IN ACCORDANCE WITH FBC FG SECS.
 502 THRU 505 OR FBC RES SEC.G2426 THROUGH G2439.
 11. PER WPB FBC 107.2.1, IN ADDITION TO THE COMBUSTION
 AIR CALCULATIONS PROVIDED FOR THE DRYER ON PLAN SHEET
 M0-2, SUBMIT COMBUSTION AIR CALCULATIONS FOR THE
 ADDITIONAL INDOOR GAS APPLIANCES. WHERE COMBUSTION AIR
 IS PROVIDED BY THE BUILDING?S MECHANICAL VENTILATION
 SYSTEM, THE SYSTEM SHALL PROVIDE THE SPECIFIED
 COMBUSTION AIR RATE IN ADDITION TO THE REQUIRED
 VENTILATION AIR IN ACCORDANCE WITH FBC FG SEC.304.9.3
 OR FBC RES G2407.9.3.
  
  
 END OF COMMENTS.
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.ALL PLANS TO BE SIGNED
 AND SEALED BY THE DESIGNER AS REQUIRED BY FAC AND FS.
  
  
 JERALD SMITH
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
 EMAIL [email protected]
 PHONE 561-805-6715
  
 19080742 125 ALHAMBRA PL
  
  
  