2019-09-16 15:25:49 | BUILDING PLAN REVIEW |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| CHRISTOPHER S. THROOP, C.B.O. |
| BUILDING PLANS EXAMINER, PX3169 |
| 1&2 FAMILY PLANS EXAMINER, SFP306 |
| CONSTRUCTION SERVICES DIVISION |
| TEL: 561-805-6726 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| 1ST REVIEW |
| |
| RESULTS: DENIED |
| |
| YOUR SUBMITTAL IS DEFICIENT FOR THE REASONS LISTED |
| BELOW. |
| ADDRESS THE ATTACHED COMMENTS AND RE-SUBMIT |
| |
| 1. INCORRECT CODE REFERENCE ON PLAN PAGE A001. CHANGE |
| FROM 2014 5TH ED. TO 2017 6TH ED. |
| CODES IN EFFECT: |
| 2017 FLORIDA BUILDING CODE, 6TH EDITION W/2017 WEST |
| PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING CODE, |
| CHAPTER 1 ADMINISTRATION |
| |
| 2. PROVIDE SOILS REPORT. |
| FBC 1803.1 GENERAL.GEOTECHNICAL INVESTIGATIONS SHALL BE |
| CONDUCTED IN ACCORDANCE WITH SECTION 1803.2 AND |
| REPORTED IN ACCORDANCE WITH SECTION 1803.6. WHERE |
| REQUIRED BY THE BUILDING OFFICIAL OR WHERE GEOTECHNICAL |
| INVESTIGATIONS INVOLVE IN-SITU TESTING, LABORATORY |
| TESTING OR ENGINEERING CALCULATIONS, SUCH |
| INVESTIGATIONS SHALL BE CONDUCTED BY A REGISTERED |
| DESIGN PROFESSIONAL. |
| |
| 3. PROVIDE SITE DRAINAGE PLAN. |
| FBC R401.3 SITE DRAINAGE |
| PROVIDE TWO SETS OF A SITE DRAINAGE PLAN SHOWING |
| COMPLIANCE WITH FBC R401.3 DRAINAGE. |
| SURFACE DRAINAGE SHALL BE DIVERTED TO A STORM SEWER |
| CONVEYANCE OR OTHER APPROVED POINT OF COLLECTION THAT |
| DOES NOT CREATE A HAZARD. |
| |
| 4. PROVIDE ENERGY SUBMITTAL. |
| FBCE-101.5.1.1.2 SIMULATED PERFORMANCE ALTERNATIVE. |
| AN ACCURATELY COMPLETED RESIDENTIAL BUILDING FORM R405 |
| (GENERATED BY COMMISSION APPROVED SOFTWARE) SHALL BE |
| SUBMITTED TO THE BUILDING OFFICIAL TO DEMONSTRATE CODE |
| COMPLIANCE BY SECTION 405. |
| |
| 5. PROVIDE PRODUCT APPROVALS FOR ALL WINDOWS AND DOORS. |
| FBC 107.3.4 ? PROVIDE PRODUCT APPROVALS FOR THOSE |
| PRODUCTS WHICH ARE REGULATED BY FAC RULE 9N-3 REVIEWED |
| AND APPROVED IN WRITING BY THE DESIGNER OF RECORD. |
| SPECIFICALLY, PROVIDE WINDOW AND DOOR SUBMITTALS. |
| |
| PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT |
| CORRECTED PAGES INTO SUBMITTAL AND LEAVE THE PREVIOUSLY |
| REVIEWED SHEETS DETACHED. |
| |
| |
| |