Plan Review Notes
Plan Review Notes For Permit 19080726
Permit Number 19080726
Review Stop G
Sequence Number 2
Notes
Date Text
2019-09-11 10:42:411) SUBMIT MANUFACTURER'S SPECIFICATIONS AND
 INSTALLATION INSTRUCTIONS FOR THE PRESSURE REGULATORS.
 REGULATORS INSTALLED ON THE EXTERIOR OF THE BUILDING
 SHALL BE APPROVED FOR OUTDOOR INSTALLATION. IDENTIFY ON
 THE SPECIFICATION SHEETS WHICH MODEL REGULATOR IS BEING
 INSTALLED AND THE ORIFICE SIZE TO ENSURE THE REGULATOR
 CAN ACCOMMODATE THE BTU LOAD THROUGH THE REGULATOR.2017
 FGC SEC.410.1, 2017 FBC-RES. SEC. G2421.1.
 2) SHOW THE CORRESPONDING EHD NUMBER OF THE CORRUGATED
 STAINLESS STEEL TUBING ON THE PLANS. 2ND REQUEST.
 3) THE PLANS SHOW THE CSST LINE AS A LOW PRESSURE LINE
 BUT THERE IS NO GAS REGULATOR SHOWN ON THE LINE AND THE
 LINE IS SHOWN CONNECTED TO THE 2 PSI PIPING.. CLARIFY.
 3) UNIONS ARE REQUIRED WITHIN ONE FOOT UPSTREAM OR
 DOWNSTREAM OF THE PRESSURE REGULATORS. FGC SEC. 410.2
 (7).
 4) SUBMIT THE APPLICABLE SIZING TABLES FOR THE LOW
 PRESSURE SECTIONS OF THE GAS SYSTEM.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW