Plan Review Notes
Plan Review Notes For Permit 19080726
Permit Number 19080726
Review Stop G
Sequence Number 1
Notes
Date Text
2019-08-22 12:54:531) ) SUBMIT TWO COPIES OF THE APPLICABLE SIZING TABLES
 USED TO SIZE THE GAS SYSTEM OR PLACE A NOTE ON THE
 PLANS/DRAWINGS SPECIFYING WHICH SIZING TABLE(S) FROM
 THE GAS CODE OR OTHER STANDARD THAT WERE USED IN THE
 DESIGN OF THIS GAS SYSTEM. REFER TO THE 2017 FBC-FUEL
 GAS SECS. 401.4, 401.8, 402.3, AND TABLES 402.4 (1)
 THRU 402.4 (37) OR 2017 FBC-RES. SEC. G2413.3, G2412.8,
 G2413.1, G2413.2, & G2413.3.
 2) SHOW THE CORRESPONDING EHD NUMBER OF THE CORRUGATED
 STAINLESS STEEL TUBING ON THE PLANS.
 3) SHOW THE LOCATION OF THE REGULATOR FOR TANKLESS
 WATER HEATER.
 4) SHOW THE BTU LOAD OF THE COOKTOP AND THE TANKLESS
 WATER HEATER ON THE PLANS.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  