Date |
Text |
2019-10-17 10:24:06 | PLAN |
| REVIEW COMMENTS |
| |
| 2ND REVIEW: 2010 FBC ELEVATION CERTIFICATE |
| ROBERT MCDOUGAL, CBO |
| COMMERCIAL COMBINATION PLANS EXAMINER |
| (561) 805-6714 |
| [email protected] |
| |
| DENIED BY BUILDING- (PREVIOUS COMMENTS HAVE NOT BEEN |
| CORRECTED) |
| PLEASE ADDRESS THE ITEMS NOTED BELOW: |
| |
| |
| THE ELEVATION CERTIFICATE THAT WAS SUBMITTED IS DENIED |
| FOR THE FOLLOWING REASONS. |
| 1) PER THE APPROVED BUILDING PLANS, THERE IS AN |
| ATTACHED GARAGE THAT IS BELOW THE REQUIRED DESIGN FLOOD |
| ELEVATION WITH FLOOD VENTS. UNDER ITEM A9 THERE IS NO |
| ATTACHED GARAGE OR FLOOD OPENINGS LISTED. |
| 2) THIS PROJECT WAS PERMITTED WHEN THE PREVIOUS FLOOD |
| MAPS WERE IN EFFECT AND THE ELEVATIONS ON THE APPROVED |
| PLANS ARE NGVD RATHER THAN NAVD. PROVIDE NOTE AND |
| CONVERSION FACTOR IN THE COMMENT SECTION. |
| 3) THE TOP OF THE BOTTOM FLOOR SHOULD BE THE ATTACHED |
| GARAGE. THE NEXT HIGHER FLOOR SHOULD BE THE FIRST FLOOR |
| OF THE RESIDENCE. THE LOWEST ELEVATION OF MACHINERY IS |
| REQUIRED TO BE AT 7.5 FT NGVD OR 6.0 FT NAVD. |
| 4) THE PHOTOGRAPHS ARE REQUIRED TO SHOW THE FLOOD |
| VENTS. |
| |
| NEW COMMENTS. |
| 5) THE ELEVATION CERTIFICATE THAT WAS SUBMITTED IS NOT |
| THE CURRENT ONE. THE CURRENT ONE HAS THE EXPIRATION |
| DATE OF NOVEMBER 30, 2018. SUBMIT THE CURRENT FORM. |
| 6) FILL IN THE FORM USING THE INFORMATION FROM THE |
| CURRENT FIRM (OCTOBER 5,2017) ADOPTED BY THE CITY OF |
| WEST PALM BEACH. USE THE PANEL NUMBER, FLOOD ZONE |
| DESIGNATION AND BASE FLOOD ELEVATION FROM THE CURRENT |
| MAP. USE THE COMMENT AREA OF SECTION D TO EXPLAIN THE |
| MAP AND ELEVATION CHANGE AND PROVIDE THE CONVERSION |
| FACTOR. |
| 7) SECTION A9(D) OF THE ELEVATION CERTIFICATE INDICATES |
| THAT (5) ENGINEERED FLOOD VENTS WERE INSTALLED. THE |
| APPROVED PLANS SPECIFY NON-ENGINEERED FLOOD VENTS WITH |
| ADEQUATE CLEAR OPENING AREA TO PROVIDE MORE THAN THE |
| REQUIRED 1000 SQUARE INCHES OF CLEAR OPEN AREA. BASED |
| ON THE ELEVATION CERTIFICATE, THE ENGINEERED FLOOD |
| VENTS DO NOT PROVIDE THE REQUIRED NET CLEAR OPENING |
| AREA OF ONE SQUARE INCH PER SQUARE FOOT OF GARAGE FLOOR |
| AREA. SUBMIT REVISED DRAWINGS AND PRODUCT APPROVALS AND |
| PRODUCT EVALUATION REPORTS FOR THE ENGINEERED FLOOD |
| VENTS. |
| 8) THE ELEVATION CERTIFICATE HAS THE LOWEST EQUIPMENT |
| AT 5.7' NGVD WHICH IS BELOW THE BFE PLUS THE 6" |
| FREEBOARD (7.5' NGVD). THE LOWEST EQUIPMENT SERVICING |
| THE BUILDING WILL HAVE TO BE RAISED TO BE AT OR ABOVE |
| THE BFE AND FREEBOARD (7.5' NGVD). |
| 9) THE COMMENT SECTION OF THE ELEVATION CERT. STATES |
| THAT THE FORMER GARAGE IS NOW A PERSONAL GYM AT |
| ELEVATION 5.6'. HABITABLE SPACE IS NOT ALLOWED TO BE |
| BELOW THE REQUIRED FLOOD ELEVATION. THIS AREA WILL HAVE |
| TO BE CONVERTED BACK TO A GARAGE AS SHOWN ON THE |
| APPROVED PLANS OR BE ELEVATED TO 7.5' NGVD. THE LATTER |
| WILL REQUIRE A REVISION TO THE APPROVED PLANS. |
| |
| |
| |