2019-08-15 18:10:59 | PLAN | | REVIEW COMMENTS | | | | 1ST REVIEW: 2010 FBC ELEVATION CERTIFICATE | | ROBERT MCDOUGAL, CBO | | COMMERCIAL COMBINATION PLANS EXAMINER | | (561) 805-6714 | | [email protected] | | | | DENIED BY BUILDING | | PLEASE ADDRESS THE ITEMS NOTED BELOW: | | | | THE ELEVATION CERTIFICATE THAT WAS SUBMITTED IS DENIED | | FOR THE FOLLOWING REASONS. | | 1) PER THE APPROVED BUILDING PLANS, THERE IS AN | | ATTACHED GARAGE THAT IS BELOW THE REQUIRED DESIGN FLOOD | | ELEVATION WITH FLOOD VENTS. UNDER ITEM A9 THERE IS NO | | ATTACHED GARAGE OR FLOOD OPENINGS LISTED. | | 2) THIS PROJECT WAS PERMITTED WHEN THE PREVIOUS FLOOD | | MAPS WERE IN EFFECT AND THE ELEVATIONS ON THE APPROVED | | PLANS ARE NGVD RATHER THAN NAVD. PROVIDE NOTE AND | | CONVERSION FACTOR IN THE COMMENT SECTION. | | 3) THE TOP OF THE BOTTOM FLOOR SHOULD BE THE ATTACHED | | GARAGE. THE NEXT HIGHER FLOOR SHOULD BE THE FIRST FLOOR | | OF THE RESIDENCE. THE LOWEST ELEVATION OF MACHINERY IS | | REQUIRED TO BE AT 7.5 FT NGVD OR 6.0 FT NAVD. | | 4) THE PHOTOGRAPHS ARE REQUIRED TO SHOW THE FLOOD | | VENTS. | | | | |
|