Plan Review Notes
Plan Review Notes For Permit 19080683
Permit Number 19080683
Review Stop G
Sequence Number 3
Notes
Date Text
2020-01-15 18:46:40APPROVED UNDER MASTER 17110874
  
 GAS PROVISO UNDER MASTER:
  
 4. THE INTAKE AND EXHAUST FOR THE BOILERS AND GENERATOR
 ARE LOCATED DOWN AT THE BOTTOM OF A SHAFT OR PIT HOW
 WILL THE EXHAUST BE KEPT FROM BUILDING UP IF THERE IS
 NO VENTILATION OF THE AREA SOME DOCUMENTATION FROM THE
 MANUFACTURE WILL BE REQUIRED STATING THAT THIS
 CONFIGURATION WILL ALLOW THE EQUIPMENT TO FUNCTION
 PROPERLY. PER WPB AMEND TO FBC 107.2.1 THE RESPONSE
 LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE
 REQUESTED DOCUMENT A SIGNED AND SEALED LETTER FROM THE
 MANUFACTURES AND THE ENGINEER. STATING THAT THIS PIPING
 LAYOUT WILL ALLOW BOTH THE GENERATOR AND THE BOILERS TO
 FUNCTION PROPERLY SIMULTANEOUSLY.
  
 PREVIOUS COMMENT NOT COMPLIED 5. SHT. P-407 PLEASE SHOW
 ON THE PLAN THE MIN DISTANCE BETWEEN THE INTAKE AND
 EXHAUST. . PER WPB AMEND TO FBC 107.2.1 THE RESPONSE
 LETTER IS NOT A CONSTRUCTION DOCUMENT PLEASE INCLUDE
 REQUESTED DIMENSIONS ON THE PLAN.
  
  