2020-01-16 12:15:38 | 2ND REVIEW FBC-2017 MECHANICAL |
| PERMIT #19080683 |
| 1/16/20 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| NFPA 110-2013 |
| NFPA 37-2015 |
| NFPA 54-2015 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEET M-101: THE GENERATOR SHALL BE INSTALLED AT A |
| MINIMUM OF 5' FROM THE EXTERIOR DOOR OPENING. PLEASE |
| SHOW THE CLEARANCE DISTANCE ON THE PLAN- SECTION 4.1.4 |
| NFPA 37. |
| |
| 2) SHEET P-102 APPROVED UNDER THE MAIN BUILDING PERMIT |
| #17110874 SHOWS A FLOOR DRAIN IN THE CENTER OF THE |
| OPEN-ROOFED GENERATOR ENCLOSURE. VERIFY THAT THERE IS |
| ADEQUATE SPACE BELOW THE GENERATOR FOR WATER TO DRAIN |
| INTO THE FIXTURE. PLEASE REVIEW THE ENCLOSURE |
| INSTALLATION DETAILS BY ENGINEERING EXPRESS AND |
| DESIGNATE WHICH METHOD WILL BE USED. SECTION 107.2.1 |
| WPB. |
| |
| 3) CONCERNING COMMENT #4D FROM THE 1ST REVIEW PRINTED |
| BELOW, THE ENGINEER OF RECORD HAS REQUESTED APPROVAL OF |
| THE GENERATOR PERMIT WITH A PROVISO PENDING A LETTER |
| FROM FLORIDA PUBLIC UTILITIES. PLEASE NOTE THAT A HOLD |
| MAY BE PLACED ON THE CERTIFICATE OF OCCUPANCY UNTIL THE |
| DOCUMENT HAS BEEN RECEIVED. |
| |
| 4D) PLEASE REVIEW SECTION 5.1.1 NFPA 110 AND PROVIDE |
| DOCUMENTATION THAT VERIFIES THE LOW PROBABILTY OF GAS |
| SERVICE INTERUPTION, OR PROVIDE ON-SITE STORAGE OF AN |
| ALTERNATE ENERGY SOURCE. |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |