Date |
Text |
2020-01-16 07:23:12 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| PREVIOUS COMMENTS THAT HAVE BEEN ADDRESSED |
| SATISFACTORILY ARE MARKED AS CORRECTED. PREVIOUS |
| COMMENTS THAT HAVE NOT BEEN ADDRESSED SATISFACTORILY |
| HAVE ADDITIONAL COMMENTS IN PARENTHESES. ANY NEW |
| COMMENTS WILL BE LISTED AFTER PREVIOUS COMMENTS. |
| |
| 1. CORRECTED, VALUE ACCEPTED. |
| 2. PROVIDE ELECTRICAL PLAN FOR REVIEW, SIGNED AND |
| SEALED BY THE PERSON RESPONSIBLE FOR THE DESIGN. WPB |
| FBC 107.2.1, 107.3.5; FS 471, 481 (THE COMMENT RESPONSE |
| REFERS TO THE ORIGINAL PERMIT 17110874. DURING THE |
| FIRST PLAN REVIEW, THE VERY FIRST COMMENT NOTED STATED |
| THE FOLLOWING: "FIRE ALARM, LOW VOLTAGE SYSTEMS, DAS, |
| LIGHTNING PROTECTION, GENERATORS, COMMERCIAL HOOD |
| SYSTEMS, WALK IN COOLERS, SIGNS, SITE LIGHTING, AND |
| SWIMMING POOLS (WHERE APPLICABLE) ARE NOT INCLUDED IN |
| THE SCOPE OF THIS PLAN REVIEW. PROVIDE A BLOCK NOTE |
| INDICATING THE REQUIRED SEPARATE PERMITS AND PLAN |
| SUBMITTALS FOR ANY OF THESE SYSTEMS PRESENT. WPB FBC |
| 105.1, 107.2.1" A NOTE WAS ADDED TO THE PLAN TO THIS |
| EFFECT. PLAN REVIEW FOR THE GENERATOR WAS NOT DONE ON |
| THE ORIGINAL REVIEW AND MUST BE COMPLETED NOW. |
| ADDITIONALLY, AS A MATTER OF PUBLIC RECORD, PLANS MUST |
| BE INCLUDED. PROVIDE ALL PLAN SHEETS THAT RELATE TO |
| GENERATOR INSTALLATION FOR REVIEW. THE SPEC SHEET FOR |
| THE GENERATOR IS NOT CONSIDERED A PLAN.) |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, PROVIDE A RESPONSE LETTER ADDRESSING EACH |
| ITEM ALONG WITH THE CITY RESUBMITTAL FORM. |
| ADDITIONALLY, INSERT CORRECTED PAGES INTO THE ORIGINAL |
| SUBMITTAL AND REMOVE THE PREVIOUSLY REVIEWED SHEETS. |
| ONE COPY OF THE PREVIOUSLY REVIEWED SHEETS SHOULD |
| REMAIN IN PACKAGE AND BE MARKED OLD SHEETS. |
| |
| SINCERELY, |
| |
| JOHN PEARSON |
| ELECTRICAL PLANS EXAMINER |
| 561-805-6746 |
| [email protected] |
| |