Plan Review Notes
Plan Review Notes For Permit 19080683
Permit Number 19080683
Review Stop M
Sequence Number 1
Notes
Date Text
2019-12-09 16:09:171ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19080683
 12/9/2019
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC FG- FLORIDA FUEL GAS CODE SIXTH EDITION 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
 NFPA 110-2013
 NFPA 37-2015
 NFPA 54-2015
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) REFER TO FIRE REVIEW COMMENTS DATED 11/6/2019 FOR
 THE EPS (GENERATOR) ROOM ENCLOSURE AND ROOM VENTILATION
 REQUIREMENTS AS LISTED UNDER NFPA 110- 2013 STANDARD
 FOR EMERGENCY AND STANDBY POWER SYSTEMS. COMPLY WITH
 THOSE COMMENTS AND THESE ADDITIONAL COMMENTS LISTED
 BELOW.
  
 2) PLEASE PROVIDE AN ENLARGED DRAWING OF THE EPS ROOM
 THAT INDICATES:
 A) FIRE RESISTANCE RATINGS OF THE WALLS AND CEILING-
 SECTION 7.2.1.1 NFPA 110.
 B) HOW THE GENERATOR WILL BE POSITIONED IN THE ROOM
 WITH CLEARANCES. IT APPEARS BY THE SUBMITTED SITE PLAN
 THAT THERE COULD BE DIFFICULTY IN COMPLYING WITH
 SECTION 7.7.4.2 NFPA 110 WHICH REQUIRES THE GENERATOR
 RADIATOR TO BE DUCTED OUTDOORS OR TO AN EXTERIOR
 OPENING BY A 2-HR RATED AIR TRANSFER SYSTEM.
 C) REQUIRED ROOM VENTILATION AND MAKEUP AIR FOR THE
 EXHAUST- SEE FIRE COMMENTS.
 D) GAS AND EXHAUST PIPING LAYOUTS IN THE ROOM.
 E) HOW COMBUSTION AIR WILL BE PROVIDED- SECTION 304 FBC
 FG. PLEASE SHOW THE MEANS AND METHOD, AND PROVIDE
 CALCULATIONS.
  
 3) ENGINE EXHAUST PIPING:
 A) SUBMIT MANUFACTURER'S PRODUCT DATA FOR THE EXHAUST
 PIPING.
 B) PROVIDE AN EXHAUST PIPING DRAWING SHOWING THE PIPING
 RUN, PIPING TYPE AND SIZE, AND EXHAUST DISCHARGE
 LOCATION WITH CLEARANCE DISTANCE MEASUREMENTS FROM THE
 TERMINATION TO MECHANICAL AND OPERABLE AIR INLETS INTO
 THE BUILDING, TO GRADE, AND TO PROPERTY LINES.
 C) PROVIDE A BACK PRESSURE CALCULATION.
  
 4) GAS PIPING:
 A) PROVIDE AN ISOMETRIC DRAWING.
 B) PROVIDE A GAS PIPING LAYOUT DRAWING SHOWING THE
 PIPING RUN FROM THE METER TO THE EPS ROOM.
 C) REFER TO SECTIONS 7.9.6, 7.9.7, & 7.9.9 NFPA 110 AND
 PROVIDE A DETAIL THAT SHOWS THE CORRECT LOCATION FOR
 EPS GAS LINE CONNECTION AND VALVE LABELING AT THE
 UTILTY METER.
 D) PLEASE REVIEW SECTION 5.1.1 NFPA 110 AND PROVIDE
 DOCUMENTATION THAT VERIFIES THE LOW PROBABILTY OF GAS
 SERVICE INTERUPTION, OR PROVIDE ON-SITE STORAGE OF AN
 ALTERNATE ENERGY SOURCE.
  
 5) DESIGN CRITERIA: PROVIDE A CURRENT LIST OF ALL
 APPLICABLE CODES AND STANDARDS USED IN THE DESIGN OF
 THE EPS PROJECT- SECTION 107.2.1 WPB.
  
 6) PLEASE CLARIFY WHY WINDLOAD ENGINEERING BY FRANK
 BERNARDO P.E. HAS BEEN SUBMITTED IF THE GENERATOR IS TO
 BE LOCATED IN AN ENCLOSED ROOM INSIDE THE BUILDING-
 SECTION 107.2.1 WPB.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  
  