Plan Review Notes
Plan Review Notes For Permit 19080683
Permit Number 19080683
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-11-06 16:09:28THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
  
 1) THERE ARE NO INDICATIONS OF THE GENERATOR EXHAUST
 SYSTEM.
  
 PLEASE PROVIDE DETAILS IN COMPLIANCE WITH ALL
 APPLICABLE NFPA 110 AND 37.
  
 7.10 EXHAUST SYSTEM.
 7.10.1 THE EXHAUST SYSTEM EQUIPMENT AND INSTALLATION,
 INCLUDING
 PIPING, MUFFLER, AND RELATED ACCESSORIES, SHALL BE IN
 ACCORDANCE WITH NFPA37, STANDARD FOR THE INSTALLATION
 AND USE OF
 STATIONARY COMBUSTION ENGINES AND GAS TURBINES, AND
 OTHER APPLICABLE
 STANDARDS.
 7.10.2 EXHAUST SYSTEM INSTALLATION SHALL BE GASTIGHT TO
 PREVENT
 EXHAUST GAS FUMES FROM ENTERING INHABITED ROOMS OR
 BUILDINGS
 AND TERMINATE IN SUCH A MANNER THAT TOXIC FUMES CANNOT
 REENTER A BUILDING OR STRUCTURE, PARTICULARLY THROUGH
 WINDOWS,
 AIR VENTILATION INLETS, OR THE ENGINE AIR-INTAKE
 SYSTEM.
 7.10.3* EXHAUST PIPING SHALL BE CONNECTED TO THE PRIME
 MOVER
 BY MEANS OF A FLEXIBLE CONNECTOR AND SHALL BE
 INDEPENDENTLY
 SUPPORTED THEREAFTER SO THAT NO DAMAGING WEIGHT OR
 STRESS IS
 APPLIED TO THE ENGINE EXHAUST MANIFOLD OR TURBOCHARGER.
  
  
 PLEASE PROVIDE DETAILS.
  
  
  
 2) THERE ARE NO INDICATIONS OF VENTILATION AIRFLOW.
  
 PER NFPA 110
  
 7.7 HEATING, COOLING, AND VENTILATING.
 7.7.1* WITH THE EPS RUNNING AT RATED LOAD, VENTILATION
 AIRFLOW
 SHALL BE PROVIDED TO LIMIT THE MAXIMUM AIR TEMPERATURE
 IN THE
 EPS ROOM OR THE ENCLOSURE HOUSING THE UNIT TO THE
 MAXIMUM
 AMBIENT AIR TEMPERATURE REQUIRED BY THE EPS
 MANUFACTURER.
  
 7.7.3 VENTILATION AIR SUPPLY SHALL BE FROM OUTDOORS OR
 FROM A
 SOURCE OUTSIDE THE BUILDING BY AN EXTERIOR WALL OPENING
 OR
 FROM A SOURCE OUTSIDE THE BUILDING BY A 2-HOUR
 FIRE-RATED AIR
 TRANSFER SYSTEM.
 7.7.4 VENTILATION AIR SHALL BE PROVIDED TO SUPPLY AND
 DISCHARGE
 COOLING AIR FOR RADIATOR COOLING OF THE EPS WHEN
 RUNNING
 AT RATED LOAD.
 7.7.4.1 VENTILATION AIR SUPPLY AND DISCHARGE FOR
 RADIATORCOOLED
 EPS SHALL HAVE A MAXIMUM STATIC RESTRICTION OF 125 PA
 (0.5 IN. OF WATER COLUMN) IN THE DISCHARGE DUCT AT THE
 RADIATOR
 OUTLET.
 7.7.4.2 RADIATOR AIR DISCHARGE SHALL BE DUCTED OUTDOORS
 OR TO
 AN EXTERIOR OPENING BY A 2-HOUR RATED AIR TRANSFER
 SYSTEM.
  
 PLEASE PROVIDE DETAILS
  
  
  
 3) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 4) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
  
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  
  