Plan Review Notes For Permit 19080683 |
Permit Number |
19080683 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-12-05 12:29:53 | BUILDING REVIEW COMMENTS: | | | | W.P.B. PERMIT: 19080683 | | REVIEWED: DECEMBER 5, 2019 | | | | DYLAN BATTLES | | BUILDING PLANS EXAMINER PX4191 | | [email protected] | | 561-805-6718 | | | | FLORIDA BUILDING CODE,6TH EDITION (2017) | | FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK | | BELOW) | | HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ | | BUILDING-PERMIT-FORMS | | FBC[B] = FBC BUILDING | | FBC[A] = FBC ACCESSIBILITY | | FBC[E] = FBC ENERGY CONSERVATION | | | | 1) 107.3.5 FBC[AMENDED]PLEASE PROVIDE A PLAN VIEW TO | | SHOW THE SIZE OF THE ROOM, SIZE OF GENERATOR AND SPACE | | PROVIDED AROUND THE UNIT. ALSO ACCOUNT FOR ACCESS DOOR | | SWINGS TO ALLOW TO FULLY OPEN. | | 2) PROVIDE DETAILS OF HOW THE UNIT CONNECTS TO FLOOR | | AND HOW PENETRATIONS FOR AIR DUCTS AND EXHAUST MEET | | CODE REQUIRMENTS. | | | | PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F | | 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME | | [email protected] | | |
|