Plan Review Notes
Plan Review Notes For Permit 19080670
Permit Number 19080670
Review Stop G
Sequence Number 2
Notes
Date Text
2019-10-01 13:09:011) SUBMIT TWO COPIES OF THE MANUFACTURER'S
 SPECIFICATION SHEETS / INSTALLATION MANUAL FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH STANDARDS NFPA 54,
 NFPA 58, AND FBC-2017 FUEL GAS CODE SEC. 402.2, AND
 301.3 OR 2017 FBC-RES. SEC. G2404.3. GAS APPLIANCES
 SHALL BE LISTED AND LABELED. THE INSTALLATION MANUALS
 FOR ALL GAS APPLIANCES / EQUIPMENT SHALL BE ONSITE AT
 THE TIME OF INSPECTION. FGC SEC.305.1, FBC-RES.
 SEC.G2408.1. 2ND REQUEST.
 2) SHOW THE LOCATION AND DISTANCE OF ANY OPERABLE DOORS
 OR WINDOWS IN RELATION TO THE TANKLESS WATER HEATER.
 THE LOCATION OF THE TANKLESS WATER HEATER SHALL COMPLY
 WITH THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE
 HOUSE PLAN / FLOOR PLAN CAN BE HAND DRAWN. WPB AMEND.
 TO FBC SEC. 107.2.1. 2ND REQUEST.
 3) A SEPARATE PERMIT IS REQUIRED FOR THE GAS
 INSTALLATION.
  
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW
 561-805-6692
 [email protected]
  
  
  
  
  