Date |
Text |
2019-10-01 13:27:46 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19080639 |
| REVIEWED: OCTOBER 1, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[AMENDED] = 2017 CHAPTER 1 WPB AMENDMENTS (SEE LINK |
| BELOW) |
| HTTPS://WPB.ORG/DEPARTMENTS/DEVELOPMENT-SERVICES/FORMS/ |
| BUILDING-PERMIT-FORMS |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[R] = FBC RESIDENTIAL |
| |
| 311.3 FBC[R] FLOORS AND LANDINGS AT EXTERIOR DOORS. |
| THERE SHALL BE A LANDING OR FLOOR ON EACH SIDE OF EACH |
| EXTERIOR DOOR. THE WIDTH OF EACH LANDING SHALL BE NOT |
| LESS THAN THE DOOR SERVED. EVERY LANDING SHALL HAVE A |
| DIMENSION OF NOT LESS THAN 36 INCHES (914 MM) MEASURED |
| IN THE DIRECTION OF TRAVEL. THE SLOPE AT EXTERIOR |
| LANDINGS SHALL NOT EXCEED 1/4 UNIT VERTICAL IN 12 UNITS |
| HORIZONTAL (2 PERCENT). |
| |
| PROVIDE LANDING AT EXTERIOR SIDE OF DOOR IF GREATER |
| THAN 2 RISERS PROVIDED. |
| |
| WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |