2019-08-16 15:24:411ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19080572
 8/16/18
  
 CODES IN EFFECT:
 FBC RES- FLORIDA RESIDENTIAL BUILDING CODE SIXTH
 EDITION 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE BEDROOM 2 & 3 TRANSFER DUCTS ARE UNDERSIZED PER
 SECTION 1602.3 FBC R.
 M1602.3 FBC-B: BALANCED RETURN AIR. RESTRICTED RETURN
 AIR OCCURS IN BUILDINGS WHEN RETURNS ARE LOCATED IN
 CENTRAL ZONES AND CLOSED INTERIOR DOORS IMPEDE AIR FLOW
 TO THE RETURN GRILL OR WHEN CEILING SPACES ARE USED AS
 RETURN PLENUMS AND FIRE WALLS RESTRICT AIR MOVEMENT
 FROM ONE PORTION OF THE RETURN PLENUM TO ANOTHER.
 PROVISIONS SHALL BE MADE IN BOTH RESIDENTIAL AND
 COMMERCIAL BUILDINGS TO AVOID UNBALANCED AIR FLOWS AND
 PRESSURE DIFFERENTIALS CAUSED BY RESTRICTED RETURN AIR.
 PRESSURE DIFFERENTIALS ACROSS CLOSED DOORS WHERE
 RETURNS ARE CENTRALLY LOCATED SHALL BE LIMITED TO 0.01
 INCH WC (2.5 PASCALS) OR LESS. PRESSURE DIFFERENTIALS
 ACROSS FIRE WALLS IN CEILING SPACE PLENUMS SHALL BE
 LIMITED TO 0.01 INCH WC (2.5 PASCALS) BY PROVIDING AIR
 DUCT PATHWAYS OR AIR TRANSFER PATHWAYS FROM THE HIGH
 PRESSURE ZONE TO THE LOW ZONE.
 EXCEPTIONS:
 1.TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER 11/2 TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT ENTERING THE ROOM OR
 SPACE IT IS SERVING AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1-INCH UNDERCUT TO ACHIEVE PROPER RETURN
 AIR BALANCE.
 2.TRANSFER GRILLES SHALL USE 50 SQUARE INCHES (OF
 GRILLE AREA) TO 100 CFM (OF SUPPLY AIR) FOR SIZING
 THROUGHTHE-WALL TRANSFER GRILLES AND USING AN
 UNRESTRICTED 1- INCH UNDERCUTTING OF DOORS TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 3.HABITABLE ROOMS ONLY SHALL BE REQUIRED TO MEET THESE
 REQUIREMENTS FOR PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND LAUNDRY ROOMS,
 EXCEPT THAT ALL SUPPLY AIR INTO THE MASTER SUITE SHALL
 BE INCLUDED.
 2) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE NEW RANGE HOOD SHALL BE ONSITE AT
 TIME OF INSPECTION. PLEASE SEE SECTION 1503.4 FBC R FOR
 MAKEUP AIR REQUIREMENTS FOR HOODS EXHAUSTING IN EXCESS
 OF 400 CFM'S.
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  