Plan Review Notes
Plan Review Notes For Permit 19080447
Permit Number 19080447
Review Stop M
Sequence Number 2
Notes
Date Text
2019-10-18 11:23:011ST REVIEW FBC-2017 MECHANICAL
 PERMIT #19080447
 10/18/19
  
 CODES IN EFFECT:
  
 FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017
 FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017
 FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION
 2017
 FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION
 2017
 FS- FLORIDA STATUTES
 FAC- FLORIDA ADMINISTRATIVE CODE
 WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH
 EDITION 2017
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) PLEASE PROVIDE A REVISON APPLICATION AND A DETAILED
 NARRATIVE TO CLARIFY THE SCOPE OF WORK FOR THIS
 SUBMITTAL- SECTION 107.2.1 WPB.
  
 2) THE ALTERNATE APPROVAL LETTER REQUEST TITLED "IBC
 104.11 ALTERNATE MEANS AND METHODS- FIRE RATED
 VENTILATION DUCT THE CANOPY HOTEL BY HILTON- PERMIT
 #16061443 BY STEVEN FELLER P.E. SHALL BE ELECTRONICALLY
 SIGNED AND SEALED- SECTION 61G15-23.005 FAC.
  
 3) IBC 104.11 ALTERNATE MEANS AND METHODS- FIRE RATED
 VENTILATION DUCT THE CANOPY HOTEL BY HILTON- SHEET
 AC-2-4 LEVEL-2 WEST: THE FLAMEBAR LAUNDRY EXHAUST DUCTS
 PENETRATING THE INTERIOR EXIT STAIR #2 APPEAR TO BE NOT
 IN COMPLIANCE WITH SECTION 1023.5 FBC B WHICH PROHIBITS
 PENETRATIONS INTO AND THROUGH THE STAIRWAY ENCLOSURE.
 PLEASE NOTE THAT NO DETAIL FOR THIS ALTERNATE
 INSTALLATION HAS BEEN PROVIDED IN THE PACKAGE, AND THE
 USE OF FLAMEBAR FOR THE INSTALLATION IS NOT INCLUDED IN
 THE FLORIDA BUILDING COMMISSION DECALARATORY STATEMENT
 DS 2016-078 THAT WAS SUBMITTED WITH THE ALTERNATE
 APPROVAL LETTER.
  
 4) SHEET M2.08A: THERE ARE VARIOUS FLAMEBAR/NON-RATED
 DUCT CONNECTORS CALLED OUT IN THE ENLARGED PENETRATION
 DETAIL. PLEASE SELECT ONE SPECIFIC CONNECTOR AND
 SUBMIIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION
 INSTRUCTIONS FOR THE CONNECTOR. PLEASE INDICATE WHERE
 THE CONNECTORS ARE SHOWN AND INCLUDED IN THE
 ALTERNATIVE APPROVAL SUBMITTAL PACKAGE.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  