Plan Review Notes For Permit 19080446 |
Permit Number |
19080446 |
|
Review Stop |
M |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2019-12-12 12:17:43 | 2ND REVIEW FBC-2017 MECHANICAL | | PERMIT #19080446 | | | | CODES IN EFFECT: | | | | FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 | | FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 | | FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION | | 2017 | | FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION | | 2017 | | FS- FLORIDA STATUTES | | FAC- FLORIDA ADMINISTRATIVE CODE | | WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH | | EDITION 2017 | | | | PLAN REVIEW RESULTS: DENIED. | | | | COMMENTS #1 & 2 FROM THE 1ST REVIEW HAVE NOT BEEN | | COMPLETELY ADDRESSED- SEE BELOW AND COMPLY. | | | | 1) PLEASE PROVIDE A REVISON APPLICATION AND A DETAILED | | NARRATIVE TO CLARIFY THE SCOPE OF WORK RELATING TO THE | | SLS PERFORMANCE BASED SMOKE ANALYSIS. | | | | 2) THE SLS PERFORMANCE BASED SMOKE ANALYSIS SHALL EACH | | BE ELECTRONICALLY SIGNED AND SEALED- SECTION | | 61G15-23.005 FAC AND SECTION 471.025 FL. STATUTES. | | | | | | WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE | | LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY | | RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT | | CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE | | PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND | | KEEP THEM WITH THE SUBMITTALS. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 401 CLEMATIS STREET | | WEST PALM BEACH FL 33401 | | 561-805-6719 | | [email protected] | | | | |
|