2019-10-18 08:56:52 | 1ST REVIEW FBC-2017 MECHANICAL |
| PERMIT #19080446 |
| |
| CODES IN EFFECT: |
| |
| FBC B- FLORIDA BUILDING CODE SIXTH EDITION 2017 |
| FBC M- FLORIDA MECHANICAL CODE SIXTH EDITION 2017 |
| FBC EC- FLORIDA ENERGY CONSERVATION CODE SIXTH EDITION |
| 2017 |
| FBC EX- FLORIDA EXISTING BUILDING CODE SIXTH EDITION |
| 2017 |
| FS- FLORIDA STATUTES |
| FAC- FLORIDA ADMINISTRATIVE CODE |
| WPB- WEST PALM BEACH AMENDMENTS TO THE FBC SIXTH |
| EDITION 2017 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) PLEASE PROVIDE A REVISON APPLICATION AND A DETAILED |
| NARRATIVE TO CLARIFY THE SCOPE OF WORK RELATING TO THE |
| FLAMEBAR SUBMITTAL AND THE SLS PERFORMANCE BASED SMOKE |
| ANALYSIS. IT APPEARS THAT THESE TWO ITEMS ARE NOT |
| RELATED BECAUSE THE USE OF THE FLAMEBAR AS AN ALTERNATE |
| TO CONSTRUCTED SHAFTS IS NOT INCLUDED IN THE ANALYSIS |
| FOR THE ATRIUM. |
| |
| 2) THE TWO SUBMITTAL DOCUMENTS- IBC 104.11 ALTERNATE |
| MEANS AND METHODS- FIRE RATED VENTILATION DUCT THE |
| CANOPY HOTEL BY HILTON BY STEVEN FELLER P.E., AND THE |
| SLS PERFORMANCE BASED SMOKE ANALYSIS SHALL EACH BE |
| ELECTRONICALLY SIGNED AND SEALED- SECTION 61G15-23.005 |
| FAC. |
| |
| 3) IBC 104.11 ALTERNATE MEANS AND METHODS- FIRE RATED |
| VENTILATION DUCT THE CANOPY HOTEL BY HILTON- SHEET |
| AC-2-4 LEVEL-2 WEST: THE FLAMEBAR LAUNDRY EXHAUST DUCTS |
| PENETRATING THE INTERIOR EXIT STAIR #2 APPEAR TO BE NOT |
| IN COMPLIANCE WITH SECTION 1023.5 FBC B WHICH PROHIBITS |
| PENETRATIONS INTO AND THROUGH THE STAIRWAY ENCLOSURE. |
| PLEASE NOTE THAT NO DETAIL FOR THIS ALTERNATE |
| INSTALLATION HAS BEEN PROVIDED IN THE PACKAGE, AND THE |
| USE OF FLAMEBAR FOR THE INSTALLATION IS NOT INCLUDED IN |
| THE FLORIDA BUILDING COMMISSION DECALARATORY STATEMENT |
| DS 2016-078 THAT WAS SUBMITTED WITH THE ALTERNATE |
| APPROVAL LETTER. |
| |
| 4) SHEET M2.08A: THERE ARE VARIOUS FLAMEBAR/NON-RATED |
| DUCT CONNECTORS CALLED OUT IN THE ENLARGED PENETRATION |
| DETAIL. PLEASE SELECT ONE SPECIFIC CONNECTOR AND |
| SUBMIIT MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| INSTRUCTIONS FOR THE CONNECTOR. PLEASE INDICATE WHERE |
| THE CONNECTORS ARE SHOWN AND INCLUDED IN THE |
| ALTERNATIVE APPROVAL PACKAGE. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |