Plan Review Notes
Plan Review Notes For Permit 19080446
Permit Number 19080446
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2019-08-13 13:33:48THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE
 MARSHAL, WITH THE FOLLOWING COMMENTS:
  
 1) THE SUBMITTED PAPERWORK DOES NOT INDICATE WHAT THE
 REVISIONS IS AND WHERE, HOW AND WHY THE REVISIONS TAKE
 PLACE.
  
 BASICALLY, WHAT CHANGED AND WHY? THERE SHOULD BE SOME
 SORT OF NARRATIVE EXPLAINING THE CHANGE.
  
 AM I TO BELEIVE THE ENTIRE DOCUMENT IS THE REVISION?
  
 PER NFPA 1
 1.14 PLAN REVIEW.
 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION
 DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND
 SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE
 CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD
 CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS.
 PLEASE SUBMIT PLANS THAT HAVE INDICATIONS WHERE THE
 REVISIONS OR MODIFICATIONS, FROM THE ORIGINAL PLANS,
 ARE LOCATED.
  
  
 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET
 REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE
 ABOVE.
  
  
 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE
 RE-SUBMITTAL OF THE ABOVE.
  
 PETER LEDUC
 FIRE MARSHAL
 561-804-4709
 [email protected]
  