Plan Review Notes For Permit 19080446 |
Permit Number |
19080446 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2019-08-13 13:33:48 | THIS PLAN WAS REVIEWED AND FAILED BY PETER LEDUC, FIRE | | MARSHAL, WITH THE FOLLOWING COMMENTS: | | | | 1) THE SUBMITTED PAPERWORK DOES NOT INDICATE WHAT THE | | REVISIONS IS AND WHERE, HOW AND WHY THE REVISIONS TAKE | | PLACE. | | | | BASICALLY, WHAT CHANGED AND WHY? THERE SHOULD BE SOME | | SORT OF NARRATIVE EXPLAINING THE CHANGE. | | | | AM I TO BELEIVE THE ENTIRE DOCUMENT IS THE REVISION? | | | | PER NFPA 1 | | 1.14 PLAN REVIEW. | | 1.14.5 WHEN REQUIRED BY THE AHJ, REVISED CONSTRUCTION | | DOCUMENTS OR SHOP DRAWINGS SHALL BE PREPARED AND | | SUBMITTED FOR REVIEW AND APPROVAL TO ILLUSTRATE | | CORRECTIONS OR MODIFICATIONS NECESSITATED BY FIELD | | CONDITIONS OR OTHER REVISIONS TO APPROVED PLANS. | | PLEASE SUBMIT PLANS THAT HAVE INDICATIONS WHERE THE | | REVISIONS OR MODIFICATIONS, FROM THE ORIGINAL PLANS, | | ARE LOCATED. | | | | | | 2) WHEN RESUBMITTING, PLEASE PROVIDE PLAN SHEET | | REVISION CLOUDS OR NUMBERED NARRATIVE RESPONSES TO THE | | ABOVE. | | | | | | 3) ADDITIONAL COMMENTS MAY BE PROVIDED ON THE | | RE-SUBMITTAL OF THE ABOVE. | | | | PETER LEDUC | | FIRE MARSHAL | | 561-804-4709 | | [email protected] | | |
|