Plan Review Notes For Permit 19080443 |
Permit Number |
19080443 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-02-19 12:19:49 | PLUMBING COMMENTS: APPROVED W/PROVISO | | | | PER WPB FBC 107.2.1 AND WPB FBC 107.3.4.1, PROVIDE AS A | | DEFERRED SUBMITTAL, REVISED PLANS TO REFLECT THE | | FOLLOWING: | | | | 1. INCLUDE A WATER RISER DIAGRAM | | 2. PROVIDE DETAIL OF ICE MACHINE DRAIN TO PUMP WITH, | | AIR GAP AND PUMP WITH MANUFACTURER'S CUT | | SHEET/SPECIFICATION AND INSTALLATION INSTRUCTIONS; | | INCLUDE DISCHARGE TO SANITARY. | | 3. SPECIFY TYPE BACKFLOW PREVENTER FOR POTABLE WATER | | SUPPLY TO THE COFFEE MAKER AND TO THE ICE MACHINE | | 4. PROVIDE DETAIL AND MANUFACTURER'S CUT | | SHEET/SPECIFICATION AND INSTALLATION INSTRUCTIONS FOR | | SS FILTRATION SYSTEM FOR COFFEE MAKER. | | | | PLANS SHALL BE SUBMITTED, APPROVED AND ON SITE PRIOR TO | | FIRST INSPECTION. | | PROCEED AT YOUR OWN RISK. | | | | | | 19080443 600 BANYAN BLVD | | | | |
|