Date |
Text |
2019-08-27 13:46:18 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19080441 |
| ADD: 505 S. FLAGLER DR. |
| CONT: ANDERSON MOORE CONTRACTING |
| TEL: 561-348-4805 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 1ST REVIEW |
| DATE: TUES. AUGUST 27/ 2019 |
| ACTION: DENIED |
| |
| 1) 002-SITE DEV. PLAN. PLEASE PROVIDE AN EXPLANATION AS |
| TO WHY THERE IS A NEW DRIVEWAY AND STAIRS BEING CUT |
| INTO S. FLAGLER DR. WHEN THE ENTRY TO THE BUILDING IS |
| ON THE WEST FACE OF THE BUILDING? 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 2) 002-SITE DEV. PLAN. IS THIS NEW DRIVE AND STAIRWAY |
| PART OF A VALET SERVICE OR DOES THE PROPOSED NEW DRIVE |
| HAVE A DROP OFF ZONE (PASSENGER LOADING ZONE) TO BE |
| INCORPORATED INTO THE DRIVE? 107.2.1.2 ADDITIONAL |
| INFORMATION IS REQUIRED. |
| |
| 3A) THERE ARE MANY ELEVATION MARKERS ON THE DRIVE PLAN |
| 002-SITE DEV. PLAN. THE ELEVATION MARKERS DO NOT MAKE |
| IT CLEAR IF THEY ARE THE TOP OF THE D CURB OR THE TOP |
| OF THE DRIVEWAY? 107.2.1.2 ADDITIONAL INFORMATION |
| REQUIRED. PLEASE NOTE DIRECTLY IN FRONT OF THE NEW |
| STAIR AND LANDING THERE IS A 0.84 FT. CROSS SLOPE DROP |
| IF THERE IS TO BE A DROP OFF ZONE (PASSENGER LOADING |
| ZONE)? 2017 FBC-ACCESS. CODE 503.4 SLOPES NOT STEEPER |
| THAN 1:48 SHALL BE PERMITTED. |
| |
| 3B) VEHICLE PULL UP SPACE IS TO COMPLY WITH ACCESS. |
| CODE REQUIREMENTS 503.2-503.4. |
| |
| 4) SHEET 002 SITE DEV. PLAN IF THERE IS NOT A PASSENGER |
| DROP OFF ZONE, THE PLANS DO NOT STATE THERE IS A |
| DROPPED CURB AT THE STAIR AND LANDING YOU WOULD HAVE TO |
| WHEEL A WHEELCHAIR SOUTH OUT INTO THE TRAFFIC LANE FOR |
| THE PARKING GARAGE TO GET TO THE SIDEWALK. 107.2.1.2. |
| ADDITIONAL INFORMATION REQUIRED. IT WOULD APPEAR THIS |
| NEW DRIVEWAY AND STAIR ARE NOT ACCESSIBLE TO THE UPPER |
| LANDING, IF NOT PLEASE PROVIDE SIGNAGE WHERE THE |
| ACCESSIBLE ENTRANCE IS LOCATED. PLEASE SHOW COMPLIANCE |
| WITH: |
| 2017 FBC-ACCESSIBILITY CODE SECTION 216.6 ENTRANCES. |
| |
| WHERE NOT ALL ENTRANCES COMPLY WITH 404, ENTRANCES |
| COMPLYING WITH 404 SHALL BE IDENTIFIED BY THE |
| INTERNATIONAL SYMBOL OF ACCESSIBILITY COMPLYING WITH |
| 703.7.2.1. DIRECTIONAL SIGNS COMPLYING WITH 703.5 THAT |
| INDICATE THE LOCATION OF THE NEAREST ENTRANCE COMPLYING |
| WITH 404 SHALL BE PROVIDED AT ENTRANCES THAT DO NOT |
| COMPLY WITH 404. |
| |
| 5) SHEET 002 SITE DEV. PLAN INDICATES THE REMOVAL OF A |
| PORTION OF A RETAINING WALL. THERE IS ALSO A NOTE |
| STAIRS BY OTHERS. WHAT IS NOT CLEAR, ARE THE STAIRS TO |
| BE PART OF SEPARATE PERMIT? THE SHEET 007L1 INDICATES |
| GRANITE STEP TREADS AND ALUMINUM HANDRAIL BUT NO PLANS |
| HAVE BEEN SUBMITTED FOR THE STAIR LAYOUT, STEEL |
| RE-ENFORCING NOR AND INFORMATION ON A HANDRAIL/ |
| GUARDRAIL SYSTEM. 107.2.1.2 ADDITIONAL INFORMATION IS |
| REQUIRED. |
| |
| 6) A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| A THOROUGH REVIEW OF THE PLANS COULD NOT HAPPEN SINCE |
| THERE WAS A GREAT DEFICIENCY IN PLANS AND REQUIRED |
| DOCUMENTATION. WITH THE NEXT PLAN REVIEW CYCLE THERE |
| MAYBE ADDITIONAL REVIEW COMMENTS BECAUSE OF NEW PLANS |
| AND INFORMATION LACKING UNDER THE PRIOR REVIEW. |
| |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |