Plan Review Notes For Permit 19080419 |
Permit Number |
19080419 |
|
Review Stop |
P |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2020-01-07 13:47:15 | PLUMBING COMMENTS: APPROVED; SEE PROVISOS ON MP-1 AND | | MP-1C | | | | 1. A BACKFLOW DEVICE (REDUCED PRESSURE ZONE PRINCIPAL | | BACKLFOW ASSEMBLY) MAY BE REQUIRED PER CITY OF WEST | | PALM BEACH UTILITIES DEPARTMENT CROSS CONNECTION MANUAL | | AND ORD #2853-95, PLEASE CALL 561-822-2240 FOR MORE | | INFORMATION SINCE THIS IS A DUAL DWELLING. | | 2. A SEPARATE GAS PLAN REVIEW WILL BE REQUIRED A GAS, A | | GAS PLAN HAS NOT BEEN INCLUDED IN THIS SUBMITTAL | | PACKAGE. A GAS PLAN REVIEW HAS NOT BEEN PERFORMED AT | | THIS TIME. A SEPARATE GAS PERMIT AND PLANS WILL BE | | REQUIRED FOR A CONTRACTOR TO PERFORM THE RELATED WORK. | | PROVIDE COMPLETE PLANS AND GAS RISER THAT REFLECTS THE | | ENTIRE SCOPE OF GAS WORK TO BE DONE AT THIS TIME PER | | THE WPB AMENDMENTS TO FBC SEC. 107.2.1. | | 3. PER FBC RES P3114.5, ACCESS SHALL BE PROVIDED TO AIR | | ADMITTANCE VALVES. SUCH VALVES SHALL BE INSTALLED IN A | | LOCATION THAT ALLOWS AIR TO ENTER THE VALVE. | | |
|