Plan Review Notes For Permit 19080419 |
Permit Number |
19080419 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2019-12-09 12:10:12 | 1) SHTS. D-1, A-1, A-2, A1C, & A-2C DO NOT BEAR THE | | SEAL OF THE DESIGN PROFESSIONAL AS REQUIRED BY FL. | | ADMIN. CODE RULE 61G1--16.001. PLEASE SEAL THE | | AFOREMENTIONED SHEETS. | | 2) SHOW THE LOCATION OF THE TANKLESS WATER HEATER FOR | | THE MAIN HOUSE ON THE ARCHITECTURAL PLANS. THE TANKLESS | | WATER HEATER IS USUALLY REQUIRED TO BE A MINIMUM OF 48 | | INCHES FROM ANY OPERABLE DOOR, WINDOW OR BUILDING | | OPENING INCLUDING SOFFIT VENTS PER THE MANUFACTURER'S | | INSTALLATION MANUAL. | | 3) SIZE ALL THE DRAINAGE LINES AND VENT LINES ON ALL | | RISER DIAGRAMS. WPB AMEND. TO FBC SEC. 107.2.1. | | 4) MASTER BATH SANITARY RISER - THE TUB, WATER CLOSET | | AND SHOWER ARE NOT VENTED. 2017 FBCR SEC. P3101.2, | | P3108.1. | | 5) ACCESS SHALL BE PROVIDED TO THE SHUTOFF VALVES FOR | | THE WASHING MACHINE. 2017 FBCR SEC. P2903.9.3. | | | | TIM LARGE | | CHIEF PLUMBING INSPECTOR | | PLUMBING PLAN REVIEW | | 561-805-6692 | | [email protected] | | | | |
|