2019-08-30 10:32:39 | CODES IN EFFECT: |
| FBC = FLORIDA BUILDING CODE 2017 6TH EDITION |
| WPB FBC = WEST PALM BEACH AMENDMENTS TO THE FBC 2017 |
| 6TH ED, CHAPTER 1. |
| FBC EC = FLORIDA BUILDING CODE ENERGY CONSERVATION 2017 |
| 6TH EDITION |
| FBC EX = FLORIDA BUILDING CODE EXISTING BUILDING 2017 |
| 6TH EDITION |
| FBC RE = FLORIDA RESIDENTIAL CODE 2017 6TH EDITION |
| NEC = NFPA 70 2014 EDITION, NATIONAL ELECTRICAL CODE |
| FS = FLORIDA STATUTES |
| FAC = FLORIDA ADMINISTRATIVE CODE |
| |
| ELECTRICAL REVIEW STATUS: DENIED, SEE COMMENTS BELOW. |
| |
| 1. VALUE FOR WORK STATED ON PERMIT APPLICATION APPEARS |
| LOW. PROVIDE COPY OF SIGNED CONTRACT WITH SCOPE AND |
| VALUE OF WORK, TO INCLUDE ALL MATERIALS AND LABOR. THIS |
| IS FOR TOTAL PROJECT, NOT JUST ELECTRICAL. WPB FBC |
| 109.3 |
| 2. ONLY ONE SERVICE PER RESIDENTIAL ADDRESS IS |
| PERMITTED. PROVIDE CORRECTION AND/OR CLARIFICATION. WPB |
| FBC 107.2.1; NEC 230.2; FBC RE E3601.2 |
| 3. PROVIDE AVAILABLE SHORT CIRCUIT CALCULATION FOR |
| SERVICE INCLUDING INFORMATION FROM THE POWER COMPANY |
| STATING WHAT THE AVAILABLE SHORT CIRCUIT CURRENT IS FOR |
| THE SERVICE TO CONFIRM THE STATED AIC RATING OF THE |
| SERVICE EQUIPMENT IS ADEQUATE. NEC 110.9, 110.10; FBC |
| RE E3606.3 |
| 4. RISER DIAGRAM SHOWS A 225 AMP DISCONNECT AND PANEL |
| FOR MAIN HOUSE. THE WIRE SIZE SHOWN FEEDING THESE ITEMS |
| IS 2/0. THIS WIRE SIZE IS NOT RATED FOR A 225 AMP |
| SERVICE. PROVIDE CORRECTION. NEC 310.15(B)(7) AND |
| (B)(16); FBC RE E3603.1, E3705.1 |
| 5. LIGHTING IN CLOSETS APPEARS TO BE STANDARD RECESS |
| LIGHTS. PER CODE, LIGHTING WITH OPEN OR PARTIALLY |
| ENCLOSED LAMPS AND PENDANT LUMINAIRES OR LAMPHOLDERS |
| SHALL NOT BE PERMITTED IN CLOTHES CLOSETS. PROVIDE |
| CORRECTION. NEC 410.16; FBC RE E4003.12 |
| 6. LIGHTING IN BATHTUB OR SHOWER AREAS SHALL BE |
| SUITABLE FOR DAMP LOCATIONS. PROVIDE CORRECTION. NEC |
| 410.10(D); FBC RE E4003.11 |
| |
| END OF COMMENTS. |
| |
| PLEASE NOTE: SUBMITTAL OF ADDITIONAL AND/OR REVISED |
| MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS. WHEN |
| RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RESUBMITTAL FORM. ADDITIONALLY, INSERT CORRECTED PAGES |
| INTO THE ORIGINAL SUBMITTAL AND REMOVE THE PREVIOUSLY |
| REVIEWED SHEETS. ONE COPY OF THE PREVIOUSLY REVIEWED |
| SHEETS SHOULD REMAIN IN PACKAGE AND BE MARKED OLD |
| SHEETS. |
| |