2019-09-16 08:20:14 | BUILDING REVIEW COMMENTS: |
| |
| W.P.B. PERMIT: 19080419 |
| REVIEWED: SEPTEMBER 16, 2019 |
| |
| DYLAN BATTLES |
| BUILDING PLANS EXAMINER PX4191 |
| [email protected] |
| 561-805-6718 |
| |
| FBC[AMENDED] = FLORIDA BUILDING CODE,6TH EDITION (2017) |
| FBC[B] = FBC BUILDING |
| FBC[EXISTING] = FBC EXISTING BUILDING |
| FBC[A] = FBC ACCESSIBILITY |
| FBC[E] = FBC ENERGY CONSERVATION |
| FBC[R] = FBC RESIDENTIAL |
| |
| 1) PROVISOS: |
| DEFERRED SUBMITTALS- |
| INTERIOR STAIRWAY, RAILS AND GUARDS |
| EXTERIOR STAIRWAY RAILS AND GUARDS |
| SEPARATE PERMITS REQUIRED FOR-LANDSCAPE, FENCES |
| CONSTRUCTION HOURS - 7AM TO 7PM MON-FRI, 8AM TO 8PM |
| SAT-SUN |
| - NO RESPONSE REQUIRED. PROVISOS WILL BE ADDED TO THE |
| PLANS AT FINAL STAMPING. |
| |
| 2) 109.3 FBC[AMENDED] PROVIDE COPY OF PROPOSAL WITH |
| CONTRACTOR TO SHOW WORK VALUE EQUAL TO THE AMOUNT SHOWN |
| ON PERMIT APPLICATION, OR ADJUST VALUE TO MATCH ACTUAL |
| COST OF WORK. PLEASE ADJUST FEE AT FRONT DESK. |
| |
| 3) 501.1.1 FBC[RE] ADDITIONS, ALTERATIONS, OR REPAIRS: |
| GENERAL. ADDITIONS, ALTERATIONS, OR REPAIRS TO AN |
| EXISTING BUILDING, BUILDING SYSTEM OR PORTION THEREOF |
| SHALL COMPLY WITH SECTION R502, R503 OR R504. UNALTERED |
| PORTIONS OF THE EXISTING BUILDING OR BUILDING SUPPLY |
| SYSTEM SHALL NOT BE REQUIRED TO COMPLY WITH THIS CODE. |
| - PLEASE PROVIDE DOCUMENTATION TO SUPPORT THE METHOD |
| CHOSEN FOR COMPLIANCE. |
| |
| 4) 408.1 FBC[R] PROVIDE VENTING CALCULATIONS FOR UNDER |
| FLOOR SPACE, OR FOLLOW REQUIREMENTS FOR UNVENTED. |
| - IF ADDITION CRAWL SPACE COMMUNICATES WITH EXISTING |
| PLEASE INCLUDE EXISTING IN CALCULATION. |
| |
| 5) 408.4 FBC[R] PROVIDE ACCESS TO THE UNDER FLOOR SPACE |
| 18X24 MINIMUM. |
| - SHOW EXISTING ACCESS, OR PROVIDE ACCESS POINT TO |
| FLOOR CRAWL SPACE IF APPLICABLE. |
| |
| 6) 806 FBC[R] SUPPLY VENTING CALCULATIONS FOR THE ATTIC |
| AND HOW THE AREA OF VENTING WILL BE ACHIEVED, OR FOLLOW |
| R806.5 FOR UNVENTED. |
| - PLEASE PROVIDE PRODUCT APPROVAL FOR ROOF INSULATION |
| AND ATTACHMENT ACCORDING TO GENERAL LIMITATIONS 7 ON |
| NOA 15-0729.18 |
| |
| 7) 806.5 FBC[R] UNVENTED ATTIC AND UNVENTED ENCLOSED |
| RAFTER ASSEMBLIES. 5.1.2. WHERE AIR-PERMEABLE |
| INSULATION IS PROVIDED INSIDE THE BUILDING THERMAL |
| ENVELOPE, IT SHALL BE INSTALLED IN ACCORDANCE WITH |
| SECTION 5.1.1. IN ADDITION TO THE AIR-PERMEABLE |
| INSULATION INSTALLED DIRECTLY BELOW THE STRUCTURAL |
| SHEATHING, RIGID BOARD OR SHEET INSULATION SHALL BE |
| INSTALLED DIRECTLY ABOVE THE STRUCTURAL ROOF SHEATHING |
| IN ACCORDANCE WITH THE R-VALUES IN TABLE R806.5 FOR |
| CONDENSATION CONTROL. |
| - PLEASE REVIEW THIS SECTION FOR AIR PERMEABLE |
| INSULATION AT ROOF DECK. |
| |
| 8) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT APPROVALS FOR |
| WINDOW MULL AND GARAGE DOORS, OR INDICATE THAT YOU |
| WOULD LIKE THEM DEFERRED. |
| - |
| |
| 9) 107.3.4.1 FBC[AMENDED] PROVIDE PRODUCT ATTACHMENT |
| FOR ROOF INSULATION, OR INDICATE THAT YOU WOULD LIKE IT |
| DEFERRED. |
| - ALSO, PROVIDE ENHANCED NAILING ENGINEERED FOR |
| EXPOSURE C IN THE 3 WIND ZONES ESTABLISHED ON SHEET |
| A-2C. PLEASE PROVIDE PRODUCT APPROVAL FOR ROOF |
| INSULATION AND ATTACHMENT ACCORDING TO GENERAL |
| LIMITATIONS 7 ON NOA 15-0729.18 |
| |
| 10) 107.2.1.2 FBC[AMENDED] SUBMIT TWO SETS OF SHOP |
| DRAWINGS FOR STAIRCASE, APPROVED BY DESIGNER OF RECORD, |
| FOR REVIEW BY WPB BUILDING DEPARTMENT AS A SUBMITTAL. |
| |
| NOTES: |
| |
| -PLEASE PROVIDE COMMENT RESPONSE SHEET TO EXPLAIN HOW |
| EACH COMMENT IS BEING ADDRESSED. |
| |
| -ADDITIONAL COMMENTS MAY BE FORTHCOMING PENDING REVIEW |
| OF MATERIALS REQUESTED. |
| |
| -WHEN RESUBMITTING, PROVIDE TWO IDENTICAL COLLATED SETS |
| OF DOCUMENTS FOR ISSUANCE. OLD SHEETS (BOTH SETS) |
| SHOULD BE RETAINED IN THE PACKAGE; PLEASE DO NOT |
| DISCARD ANY DOCUMENTS. THEY SHOULD BE BOUND TOGETHER |
| SEPARATELY FROM THE TWO ISSUANCE SETS AND MARKED "VOID" |
| OR "OLD SHEETS". PLEASE DO NOT STAMP THE PLANS VOID AS |
| APPLICANTS ARE INADVERTENTLY STAMPING SHEETS THAT WE |
| NEED "VOID", RENDERING THEM NOT USABLE. |
| |
| PLEASE FEEL FREE TO CONTACT ME AT 561-805-6718 (M-F |
| 8-5) TO DISCUSS COMMENTS, OR E-MAIL ANYTIME |
| [email protected] |
| |
| |
| |