Notes |
Date |
Text |
2019-09-24 16:11:44 | PLUMBING COMMEMTS: APPROVED W/PROVISO | | REFERENCE PLAN SHEET P-1: | | 1. HORIZONTAL FIXTURE DRAIN FROM WASHER TO EXISTING | | WASTE STACK SHALL BE 3 INCH DIAMETER PER STUDOR DESIGN | | MANUAL, FIGURE 11, OR PROVIDE A CONVENTIONAL INDIVIDUAL | | VENT AND CONNECT TO VENT STACK IN LIEU OF STUDOR VENT. | | 2. PROVIDE VERTICAL RISE ON RELIEF (BACK) VENT PER FBC | | PL 905.3 AND 905.4. | | 3. A 1ST ROUGH PLUMBING INSPECTION IS REQUIRED PRIOR TO | | SHOWER PAN INSTALLATION TO DETERMINE THAT FLOOR | | PENETRATIONS ARE PROPERLY FIRE SAFED. SEE REDLINED | | COMMENTS. | | 4. WASHER SHUT OFF VALVES SHALL BE ACCESSIBLE PER FBC | | PL 606.2. | | |
|