Date |
Text |
2019-09-30 13:08:17 | 2017 FBC- BUILDING PLAN REVIEW |
| W. P. B. PERMIT: 19080396 |
| ADD: 2425 PRESIDENTIAL WAY SUITE: 403 |
| CONT: USHER AND ASSOCIATES |
| TEL: 561-543-2185 |
| E-MAIL: [email protected] |
| |
| 2017 FLORIDA BUILDING CODE W 2017 WEST PALM BEACH |
| AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1, |
| ADMINISTRATION. |
| |
| 2017 EXISTING BUILDING CODE. 801.3 COMPLIANCE. ALL NEW |
| CONSTRUCTION ELEMENTS, COMPONENTS, SYSTEMS, AND SPACES |
| SHALL COMPLY WITH THE REQUIREMENTS OF THE FLORIDA |
| BUILDING CODE, BUILDING. |
| |
| 2ND REVIEW |
| DATE: MON. SEPT. 30/ 2019 |
| ACTION: DENIED |
| |
| 1A-B) COMPLIED. |
| |
| 2) 2ND REVIEW SAME COMMENTS. SPOKE WITH THE CONTRACTOR |
| TODAY ABOUT THE PRODUCT SAM 90 VERSES SUPER SAM 125. |
| SAM 90 DOES NOT MEET THE IIC RATING OF 50 ON A 6 INCH |
| CONCRETE SLAB, NO DROPPED CEILING. PLEASE NOTE THE |
| SUBMITTED SALES BROCHURE DOES NOT HAVE THE CORRECT DATA |
| AND TESTING RESULTS TO OBTAIN A PERMIT. WE HAVE TO DATE |
| NOT PERMITTED THE PRODUCT SAM 90 CONTROL MEMBRANE. WE |
| DO HAVE THE ACTUAL TEST RESULT THAT HAVE PASSED FOR |
| SUPER SAM125. |
| |
| BLDG TYPE: TYPE I/ TYPE II FLOOR INSULATION (FBC-B |
| 2017) |
| FOR TILE, STONE, MARBLE, VINYL AND WOOD FLOORING ALL |
| NEED TO HAVE HAD THE SOUND UNDERLAYMENT TESTED FLOOR |
| ASSEMBLIES TO THE FOLLOWING STANDARDS AND MEET THE |
| QUALIFICATIONS LISTED UNDER EACH OF THE STANDARDS FOR A |
| 6 INCH CONCRETE FLOOR ASSEMBLY/ NO DROPPED CEILING: |
| PLEASE PROVIDE TEST REPORTS SHOWING COMPLIANCE WITH: |
| |
| 2A) FBC-B 2017 1207.3 STRUCTURE-BORNE SOUND. |
| FLOOR/CEILING ASSEMBLIES BETWEEN DWELLING UNITS OR |
| BETWEEN A DWELLING UNIT AND A PUBLIC OR SERVICE AREA |
| WITHIN THE STRUCTURE SHALL HAVE AN IMPACT INSULATION |
| CLASS (IIC) RATING OF NOT LESS THAN 50 (45 IF FIELD |
| TESTED) WHEN TESTED IN ACCORDANCE WITH ASTM E 492. |
| |
| 2B) FBC-B 2017 1207.2 AIR-BORNE SOUND. |
| WALLS, PARTITIONS AND FLOOR/CEILING ASSEMBLIES |
| SEPARATING DWELLING UNITS FROM EACH OTHER OR FROM |
| PUBLIC OR SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION |
| CLASS (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) |
| FOR AIR-BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM |
| E 90. |
| |
| 2C) FLAME SPREAD- FBC-B 2017 603.1. EXCEPTION 2. |
| INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID |
| DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED |
| TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200. |
| |
| FLAME SPREAD INDEX. A COMPARATIVE MEASURE, EXPRESSED AS |
| A DIMENSIONLESS NUMBER, DERIVED FROM VISUAL |
| MEASUREMENTS OF THE SPREAD OF FLAME VERSUS TIME FOR A |
| MATERIAL TESTED IN ACCORDANCE WITH ASTM E 84 OR UL 723. |
| |
| 3) IN ACCORDANCE WITH SECTION 553.79 F. S. THIS IS TO |
| ADVISE YOU OF THE OWNERS OR OPERATORS RESPONSIBILITY TO |
| COMPLY WITH THE STATE & FEDERAL ASBESTOS REGULATIONS, |
| INCLUDING SECTION 376.60 F. S. AND CFR 61- NESHAP |
| REQUIREMENTS. PLEASE PROVIDE A SIGNED ACKNOWLEDGEMENT |
| FROM THE CONTRACTOR, ON LETTERHEAD, STATING THAT THE |
| INSTRUCTIONS ON THE WEBSITE OF ASBESTOS PROGRAM |
| COORDINATOR, FLORIDA DEPARTMENT OF HEALTH PALM BEACH |
| COUNTY WILL BE FOLLOWED AND THAT NOTIFICATION WILL BE |
| GIVEN TIMELY. ADDITIONAL INFORMATION REGARDING ASBESTOS |
| REQUIREMENTS CAN BE FOUND ON THEIR WEBSITE: |
| |
| HTTP://PALMBEACH.FLORIDAHEALTH.GOV/PROGRAMS-AND-SERVICE |
| S/ENVIRONMENTAL-HEALTH/AIR-QUALITY/_DOCUMENTS/ASBESTOS- |
| NOTIFICATION-FORM-PBC-FILLABLE-UPDATE-07-30-2015.PDF |
| |
| 901 EVERNIA STREET |
| WEST PALM BEACH, FL 33401 |
| (561) 837-5900 ASBESTOS PROGRAM COORDINATOR |
| THE CONTRACTOR ACKNOWLEDGEMENT CAN BE SENT VIA EMAIL TO |
| [email protected]. THE INFORMATION SHOULD BE IN PDF |
| FORMAT AS AN ATTACHMENT TO THE EMAIL. PLEASE INCLUDE |
| THE PERMIT NUMBER AND ?ASBESTOS? IN THE SUBJECT LINE. |
| |
| 4) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION |
| & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS |
| NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL |
| REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE |
| REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO |
| EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| COOPERATION. |
| |
| JAMES A. WITMER BN, PX, CBO |
| SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| BUILDING DIVISION / DEVELOPMENT SERVICES DEPARTMENT |
| 401 CLEMATIS ST. WEST PALM BEACH. FL 33402 |
| TEL: 561-805-6717 |
| FAX: 561-805-6676 |
| E-MAIL: [email protected] |
| |
| |
| |